S y n e r g i z e   R F   I L C   I n s t a l l a t i o n   I n s t r u c t i o n s

7

2.   

Open the door, and remove the four screws securing the high voltage barrier 

to the enclosure.

3.   

Configure the 24 volt relays by moving the associated jumper to set the 

desired configuration.
ILC devices are shipped from the factory with the 24 volt relays configured 

as normally closed relays. If normally open relays are desired, move the 

associated jumper so that it shorts the center and N.O. pins. Refer to the 

table and images below for more information.

Port

Relay

Jumper

Port 1

K1

J11

Port 2

K3

J12

Содержание Synergize RF

Страница 1: ...Synergize RF Network Intelligent Load Control ILC Device Installation Instructions Y99854 3 TUM Revision B www Aclara com...

Страница 2: ......

Страница 3: ...re or firmware described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license Disclaimer The information in this document is subjec...

Страница 4: ......

Страница 5: ...FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and...

Страница 6: ...m from all persons during normal operation This device is not designed to operate in conjunction with any other antennas or transmitters No other operating instructions for satisfying RF exposure comp...

Страница 7: ...limites sont con ues pour offrir une protection raisonnable contre l interf rence nuisible dans une installation r sidentielle Cet quipement g n re utilise et peut mettre de l nergie de fr quences ra...

Страница 8: ...l n a aucun branchement externe pour tre utilis en association avec toute autre antenne ou tout transmetteur Aucune autre instruction d utilisation n est requise pour assurer la conformit aux r gles d...

Страница 9: ...s trees or hills provide minimum obstructions Refer to MTU Installation Requirements Y20255 TEB for additional information Power Source The ILC device must be sourced from a dedicated 5 amp breaker In...

Страница 10: ...ocedure 0 10 in lbs torque limiting screwdriver Installation Instructions NOTES Only copper conductors should be used Wire gauge is load dependent for relays and Aclara specifies a range of 30 to 10 A...

Страница 11: ...4 volt relays by moving the associated jumper to set the desired configuration ILC devices are shipped from the factory with the 24 volt relays configured as normally closed relays If normally open re...

Страница 12: ...y line and desired load connections using compatible conduit fittings such as the Hubbell P050NGYA for conduit The ILC device supports 50 60Hz input power for 208 to 277VAC Refer to the following tabl...

Страница 13: ...ion from the end of each wire so as to make a good connection without leaving any copper exposed NOTE ILC device tamper detection requires that the input power and any connected relay ports use the sa...

Страница 14: ...i z e R F I L C I n s t a l l a t i o n I n s t r u c t i o n s Wiring Diagram Wiring Diagram The following image provides a system and wiring overview that may be helpful for successfully installing...

Страница 15: ...install the inner cover by torquing four screws to 10 in lbs and close the other door without locking it 8 Re apply power to the ILC device and verify the green Power LED is on The amber Demand LED ma...

Страница 16: ...g Diagram 9 If the fault LED light is not illuminated verify the door is closed and torque the screw to 1 in lb with a low speed driver below 400 rpm Secure the door screw with a utility approved lock...

Страница 17: ...e LEDs are visible through the holes in the inner cover of the ILC device as shown in the following image Observing a solid blue light through the inner cover vents within 5 minutes of power up indica...

Страница 18: ...ng red Loads across relays wired incorrectly unit not energized Remove power from loads and ILC and correct wiring Request a remote reset register 35 if re powering unit does not extinguish LED Initia...

Страница 19: ...t have access to Aclara Connect email support aclara com and request access Aclara University Aclara s on demand training makes content available to you in a convenient cost effective online environme...

Отзывы: