A panel mounting kit option, ref WLg-FIX-PLT, is available. It contains 3
screws and a right angle bracket. It must be assembled instead of the din rail
clip.
ALARM CONTACTOR
The product provides an alarm contactor in order to signal a predefined event
to the user.
Power connector pins 5 and 6 are used to achieve this goal. This contactor is
open at quiescent state and closes when the alarm condition occurs. It is
closed as well when the product is powered off or not in an operational state.
This is a first stage alarm contactor which must not be used to drive power
directly. To carry out this function, please consider the use of a power relay
(as shown by the picture below).
Moreover, neither surge nor ESD protections are provided in order to keep
correct insulation. Please set up your own protection devices if needed.
The alarm contact can switch a 60V maximum voltage for a 150 mA
maximum current.