background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 6.0

I0000701

FIGURE 1: 

ENCLOSURE DIMENSIONS

WIRELESS REMOTE/STRAP-ON

TEMPERATURE SENSORS

Installation & Operation Instructions

SST5630

Phone:

 1-888-967-5224

Website:

 workaci.com

the data transmission has been received successfully.  The Data-Link LED will continue to blink once for 
every data transmission.  The data transmission rate is programmed into the sensor (normally 75 second 
intervals). To manually initiate a data transmission press the push button switch located by the negative 
terminal of the battery.

MOUNTING INSTRUCTIONS

ENCLOSURE MOUNTING

The enclosure must be mounted outside of the freezer/cooler. On Vertical units, mount on the top of the 
freezer see 

Figure 2

. On Horizontal units, mount on the backside or side of the freezer. Attach the base 

directly to the wall by using double sided tape. 

WIRE INSTALLATION

ACI recommends installing the wire through the 
door seal, probe access port, or cooler wall. On 

horizontal units, the preferred method is using the 
rear door seal as shown in 

Figure 3

. On vertical 

units, remove the rear panel. There is typically a 
probe access hole. Probe and wires can be ran into 

that access hole. Alternatively, you can drill a hole 
just larger than the diameter of the wire (0.125” 

(3.175 mm)) through the wall. From inside the 
cooler/freezer, push the wire through the hole. Use 

mounting clips to secure the wire to the interior wall 
or shelving. Use silicone caulking to seal the hole 

around the wire.

2.56"

4.53"

2.23"

Battery Positive 

Terminal

Internal Link 

Button

SST5630AE

Altech Water 

Tight Fitting 

NEMA 4X Enclosure

10' Cable

2.00" x 0.187" Probe

GENERAL INFORMATION

The SST5630 is a battery operated spread spectrum 
wireless remote/strap-on temperature sensor.  It is 
designed for monitoring refrigeration or freezers 
from -300°F (-184°C) to 300°F (149°C).

The RTD sensor is encapsulated in a 0.187” O.D. 304 
stainless steel probe (2” probe length) for single 
point pipe temperature monitoring.

ACI’s wireless sensors utilize reliable Spread 
Spectrum Radio technology.  They can be installed 
easily in minutes eliminating hundreds of feet of 
wire and saving installation cost while reducing 
installation labor risks.

The sensor Data-Link LED confirms the data 
transmission was received by the receiver for fast 
and reliable positioning of the sensor during 
installation.  There is no need for special wireless installation equipment or tool.

Together with the ACI receivers and controllers, the ACI wireless sensors can be used with any LON works, 
BACnet, Modbus, system or panel.

The maximum radio transmission distance is dependent on the building type. In a typical commercial 
building with steel I-Beam construction, concrete floors with reinforcing rod, and metal stud walls, it can be 
expected that transmissions will penetrate vertically typically one floor below and one floor above a 
transceiver/receiver, and horizontally through 200 to 300 feet of walls, furniture and air. 

MOUNTING INSTRUCTIONS

Wireless sensors should be installed within 200 to 300 feet of the receiver.  RR2552 signal repeaters can be 
installed as to increase transmission distance between sensors and receivers.

CAUTION:
Observe battery polarity when installing battery.

To select the proper sensor location, first install and power the receiver.  To activate the sensor insert the 
battery observing the polarity. 

While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times 
every 10 seconds.  Once a connection has been established the Data-Link LED will blink once to indicate 

SENSOR MOUNTING

Bullet Probe sensors can be wrapped around a shelf as 

 

shown in 

Figure 4 

(p.2). Alternatively, the sensor 

may be mounted on walls using a mounting clip. The sensor should be mounted in an area where air 
circulation is well-mixed and not blocked by obstructions. Slide the sensor probe through the mounting 
clip - see 

FIGURE 5 (p.2). 

Drill a 1/4” screw through the socket and tighten to the wall. If a thermal buffer is 

required, use a glycol kit (ACI Item #130127). Drill pilot holes for the provided mounting screws. Use the 
mounting clip holes as a guide - see 

FIGURE 6 

(p.2). Drill the #10-16 x 1/2“ screws through the bracket 

holes and fasten it to the wall. Insert the bottle into the bracket, and make sure it is seated securely.

Note:

 When using in tank or glycol application, the sensor cannot be fully submerged. The back end of the 

probe (where the wire enters), must be kept above the liquid. 

Locate and record the sensor ID numbers located on a label inside the unit prior to mounting.

The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low.  A 
low battery signal is also sent to the receiver for remote indication that the battery should be replaced.  If 
the battery is not replaced in approximately 2 months, the battery voltage will become so low that the Low 
Battery and Data-Link LEDs will not blink.  Replace the battery and the Data-Link LED will start blinking 
while the sensor is re-establishing communications with the receiver.
Then attach the cover of the sensor by installing the four screws.

PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL 
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE 
MAY BE AFFECTED.

Содержание SST5630

Страница 1: ...er for fast and reliable positioning of the sensor during installation There is no need for special wireless installation equipment or tool Together with the ACI receivers and controllers the ACI wireless sensors can be used with any LON works BACnet Modbus system or panel The maximum radio transmission distance is dependent on the building type In a typical commercial building with steel I Beam c...

Страница 2: ...directly to the wall by using double sided tape WIRE INSTALLATION ACI recommends installing the wire through the door seal probe access port or cooler wall On horizontal units the preferred method is using the rear door seal as shown in Figure 3 On vertical units remove the rear panel There is typically a probe access hole Probe and wires can be ran into that access hole Alternatively you can dril...

Страница 3: ...The back end of the probe where the wire enters must be kept above the liquid Locate and record the sensor ID numbers located on a label inside the unit prior to mounting The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low A low battery signal is also sent to the receiver for remote indication that the battery should be replaced If the battery is ...

Страница 4: ...Dimensions Cable Length Cable Type Fitting Data Protocol RF Characteristics Sensor Data Transmission Time Transmission Distance Enclosure Material Flammability Rating Battery 1 Duracell DL123A Lithium 3V 1400 mAh 45 mA maximum 2 3 years typical 14 to 140ºF 10 to 60ºC 5 to 65 Non condensing 0 to 140ºF 17 70 to 60ºC 5 to 65 RH Non condensing 300 to 300ºF 184 to 149ºC 1ºF 0 555ºC 12 bit resolution Le...

Отзывы: