background image

WARRANTY

The ACI Wireless Series are covered by ACI’s Two (2) Year Limited Warranty, which is located 
in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: 
www.workaci.com.

W.E.E.E. DIRECTIVE 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling 
centre. Do not dispose of with household waste. Do not burn.

PRODUCT SPECIFICATIONS

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 6.0

I0000701

Input Voltage:

Battery Life:

Operating Temperature Range:

Operating Humidity Range:

Storage Temperature Range:

Sensor Range:

Accuracy:

Probe Dimensions:

Cable Length  |  Cable Type:

Fitting:

Data Protocol:

RF Characteristics:

Sensor Data Transmission Time:

Transmission Distance:

Enclosure Material  |  

Flammability Rating:

Battery; 1 (Duracell DL123A), Lithium 3V 1400 mAh 45 mA maximum 

2-3 years typical

14 to 140ºF (-10 to 60ºC) 

5 to 65%, Non-condensing

0 to 140ºF (-17.70 to 60ºC), 5 to 65% RH, Non-condensing

-300 to 300ºF (-184 to 149ºC)

+/- 1ºF (+/- 0.555ºC) 12 bit resolution

Length:

 2.0” (50.80 mm)  |  

Diameter:

 0.188” (4.78 mm)  |  

Material:

 304 stainless steel

10’ (3.05m)  |  CL2P plenum rated

Nylon 6/6, Flammability rating UL94V-2

IEEE 802.15.4-2003/2006

900 MHz, Operating Frequency 10 channels between 902 – 928 MHz

Transmitter Power:

 11 dBm  |  

Receiver Sensitivity:

 -11 dBm 

75 seconds (default)  |  300 seconds (optional)

200 – 300 ft horizontally depending on building type and construction, and typically one floor

above and below the transceiver vertically

Polycarbonate Plastic  |  UL94-HB

Содержание SST5630

Страница 1: ...er for fast and reliable positioning of the sensor during installation There is no need for special wireless installation equipment or tool Together with the ACI receivers and controllers the ACI wireless sensors can be used with any LON works BACnet Modbus system or panel The maximum radio transmission distance is dependent on the building type In a typical commercial building with steel I Beam c...

Страница 2: ...directly to the wall by using double sided tape WIRE INSTALLATION ACI recommends installing the wire through the door seal probe access port or cooler wall On horizontal units the preferred method is using the rear door seal as shown in Figure 3 On vertical units remove the rear panel There is typically a probe access hole Probe and wires can be ran into that access hole Alternatively you can dril...

Страница 3: ...The back end of the probe where the wire enters must be kept above the liquid Locate and record the sensor ID numbers located on a label inside the unit prior to mounting The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low A low battery signal is also sent to the receiver for remote indication that the battery should be replaced If the battery is ...

Страница 4: ...Dimensions Cable Length Cable Type Fitting Data Protocol RF Characteristics Sensor Data Transmission Time Transmission Distance Enclosure Material Flammability Rating Battery 1 Duracell DL123A Lithium 3V 1400 mAh 45 mA maximum 2 3 years typical 14 to 140ºF 10 to 60ºC 5 to 65 Non condensing 0 to 140ºF 17 70 to 60ºC 5 to 65 RH Non condensing 300 to 300ºF 184 to 149ºC 1ºF 0 555ºC 12 bit resolution Le...

Отзывы: