AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000684
Middleton, Wisconsin 53562
Page 3 of 4
PRECAUTIONS
S
ENSORS
,
REPEATERS AND RECEIVERS SHOULD
NOT
BE INSTALLED IN THE FOLLOWING AREAS
:
•
I
NSIDE METAL ENCLOSURE
/
PANEL
•
INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT
/
ELEVATOR BANKS
•
IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
T
RANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED
.
CAUTION
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS
WHERE HUMAN LIFE MAY BE AFFECTED
.
PRODUCT SPECIFICATIONS
Supply
Voltage
(1) Li/MnO2 3.0 VDC Battery, 1400 mAH (e.g. Duracell DL123A)
RF
Data Protocol
IEEE 802.15.4-2003/2006
Operating Frequency
902-928 MHz
Output Power
+11 dBm
Receiver Sensitivity
-110 dBm
Open Field Range
One mile (line of sight)
Data Transmission Interval
75 seconds (standard), 300 seconds (option)
Temperature Accuracy
± 1
°
F
Sensor Operating Range
-40 to 200
°
F (-40 to 93
°C
)
Features
User Interface
20’ (6.1m) sensor cable length
and External Link Button (optional)
Enclosure
Material
ABS (standard), Polycarbonate (Nema 4X)
Rating
UL 94 5VA (standard), UL 94 HB (Nema 4X)
Environment Operating Temperature
32 to 140F (0 to 60°C)
Operating Humidity
5 to 95% RH (non-condensing)
Approvals
FCC
WARRANTY SPECIFICATION
The ACI Wireless Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site:
!
!