MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562
Page 7 of 33
www.workaci.com
(888) 967-5224
•
Our recommendation is not to change the default factory IP address of the transceiver,
since the Ethernet connection is used to configure the transceiver only and will not be
required when the LON network is up and running.
•
Router Setup – Webserver Only
–
NOT USED
.
d.
Manually Resetting The Factory Default IP Address
•
The Transceiver can manually be reset to the default IP Address by moving the jumper
(J6) from “Norm” to “Init”.
•
Turn off the power to the Transceiver and move the jumper from “Norm” to “Init”. Turn
on power and the Transceiver can be communicated with using the Factory Default IP
Address 192.168.0.1 Subnet Mask 255.255.255.0. The Config File is no longer active
while the jumper is in the “Init” position . A new Config File can be downloaded to the
Transceiver if desired.
•
To reactivate the Config File - turn off the power to the Transceiver and move the
jumper back to “Norm”. Turn the power back on and the Config File will become
active. The Transceiver will have the IP Address that was set in the Config File.