MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562
Page 5 of 33
www.workaci.com
(888) 967-5224
II.
LON Transceiver Installation & Network Setup
a.
Transceiver Installation
•
Choose a location close to the LonWorks® network connection awat from the ground.
•
Mount the Transceiver on the wall using four #8 screws.
•
24 VAC Input (500 mA nominal) - Connect 24VAC 60 Hz (no secondary ground) to the
input terminals using 20 AWG wire as shown in the product data sheet.
Figure 1
•
FTT-10 - Use 20 or 22 gauge shielded twisted pair wire to connect the
Transceiver(Terminals “A” & “B”) to the LonWorks network (See Figure 1). The
connection of the FTT-10 network is not polarity sensitive and the designation (+) and (-)
on the board is not relevant in this case. There are two sets of terminal “A” & “B”. The
second set of terminals can be used to extend the FTT-10 network (if needed).
Default
IP
Jumper
TCP/IP
Connection (J2)
Connection
(J1)
24 VAC
Input
RS485
Terminals