background image

FIGURE 2: 

ASSEMBLY

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 2

Version: 3.0

I0000230

MEDIA COMPATIBILITY

The bulk micro-machined transducer features a stainless steel diaphragm with welded construction that 
contains no O-rings, which makes them compatible with any gas or liquid that’s compatible with 304L 
stainless steel.  Some compatible gasses and liquids include refrigerants, glycol, motor oil, diesel, hydraulic 
fluid, brake fluid, water, waste water, hydrogen, nitrogen and air.

INSTALLATION

LOCATION

Install the sensor in a location where it will not be exposed to extreme temperatures, vibration or shock.  
Install the pressure sensor above or on the side of pipes, in a location where liquid will not drip on the unit.  
Condensation can potentially build up and run down the harness, position the unit and harness so water 
does not pool on the back of the sensor.  Do not install the sensor at the end of a long run of pipe.  

CONNECTION

The GP uses a standard ¼”-18 NPT external 
fitting.  Standard pipe fittings and installation 
procedures should be used during installation.  
Install pipe tape, thread sealant or other 
suitable pipe compound when connecting the 
sensor to the pressure source or any of the 
accessories.  For pressure ranges more than 500 
PSI (3447.4 kPa), we recommend the use of a 
sealant such as Loctite Hydraulic Sealant.  Do 
not use excessive amounts of sealant or you 
might block the pressure going into the 
transducer.  Install the device using a wrench on 
the hex flats provided.  Do not use a strap 
wrench on the body.  When installing the GP 
sensor, the torque limit is 150 in lbs (16.95 Nm), 
Do Not over tighten.  Overtightening metal 
fittings may cause a slight zero shift.  The use of 
plastic fittings typically results in no noticeable 
zero shift.  The torquing effect does not 
appreciably affect linearity or sensitivity.  In 
liquid pressure monitoring applications, air 
present in the lines will cause erratic readings, 
use bleed fittings to bleed off any air that has 
been trapped before transducer installation.  

WIRING INSTRUCTIONS

The transducer requires a supply voltage of +13 
to 30 VDC with a minimum supply current of 25 
mA (per unit) to power the loop.  The transducer 
is equipped with a Packard connector for easy 
installation, and is designed for use with the GP 
Harness.  Install the GP Sensor onto the harness 
then make the proper connections to the 
harness.  Connect the Power lead (Red) to the plus terminal of the supply voltage.  Connect the Return lead 
(White) to the Analog Input(+) terminal of the current measuring device(controller).  Connect the 
Common(-) terminal of the current measuring device to the Common(-) terminal of the supply voltage. If 
the unit is equipped with a Shield Wire, it should be connected to the system or earth ground.  See 

Figure 

3 (p. 3)

, wiring diagram. 

Note:

 Black wire is not used.

SHUT OFF VALVE

SHUT OFF VALVE

PRESSURE 

TRANSDUCER

PRESSURE 

TRANSDUCER

PRESSURE SNUBBER

SYPHON (OPTIONAL)

(OPTIONAL)

SUPPLY LINE

SUPPLY LINE

Содержание GP Series

Страница 1: ...e life of your sensor by smoothing out pressure spikes surges and pulsations and prevent debris from collecting in the sensor diaphragm opening The A 0 25 Snubbers are made of 316 Stainless Steel and should be used with compatible materials Syphons The A Syphon must be used to protect the sensor from extreme operating temperatures when the operating temperature of the steam being monitored is high...

Страница 2: ...t use excessive amounts of sealant or you might block the pressure going into the transducer Install the device using a wrench on the hex flats provided Do not use a strap wrench on the body When installing the GP sensor the torque limit is 150 in lbs 16 95 Nm Do Not over tighten Overtightening metal fittings may cause a slight zero shift The use of plastic fittings typically results in no noticea...

Страница 3: ...gnal is Inaccurate SOLUTION S ConfirmtheDCsupplyvoltageis 4 20mAOutput 250OhmLoad 13to30VDC 500OhmLoad 18 to 30VDC DisconnectthesensorfromthelinetoensureNoderisorsedimentis blockingtheinletportofthetransducer Determinethattheproperoutputisbeingtransmittedbasedonthe predetermined span Measure the output of the transmitter with a handheld multimeter and compare the measured output to calculate outpu...

Страница 4: ...teel 1 4 18 NPT 800 Ω 24 VDC Formula Supply VDC 8 VDC 0 020 A 15 to 300 psig 3x FS 500 psis 3x FS 0 to 95 RH non condensing Any gas or liquid compatible with 304L Stainless Steel 150 lbs in 16 95 Nm SENSOR NON SPECIFIC INFORMATION Supple Voltage Supply Current Output Signal Accuracy1 22 C 71 6 F Thermal Error 40 to 105 C Stability 250 Hours 225 F 125 C Operating Storage Temperature Ranges Process ...

Отзывы: