background image

FIGURE 3: 

WIRING DIAGRAM

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 3

Version: 3.0

I0000230

Optional 250 Ohm or 500 Ohm

Load Resistor for a 1-5 VDC or

2-10 VDC Output

TROUBLESHOOTING

PROBLEM

No Output or Output Signal Reading Low:

Output Signal is Inaccurate:

SOLUTION(S)

Confirm the DC supply voltage is:.

4-20 mA Output: 250 Ohm Load: +13 to 30 VDC | 500 Ohm Load: +18 
to 30 VDC.

Disconnect the sensor from the line to ensure No deris or sediment is 

blocking the inlet port of the transducer.

Determine that the proper output is being transmitted based on the 

predetermined span. Measure the output of the transmitter with a 
handheld multimeter and compare the measured output to calculate 
output.

COM

RED WIRE

WHITE WIRE

SHIELD

BLACK WIRE NOT USED

FOR 4-20mA

POWER SUPPLY

 +13 TO 30 VDC

-   +

AUTOMATION

      PANEL

AI1

Содержание GP Series

Страница 1: ...e life of your sensor by smoothing out pressure spikes surges and pulsations and prevent debris from collecting in the sensor diaphragm opening The A 0 25 Snubbers are made of 316 Stainless Steel and should be used with compatible materials Syphons The A Syphon must be used to protect the sensor from extreme operating temperatures when the operating temperature of the steam being monitored is high...

Страница 2: ...t use excessive amounts of sealant or you might block the pressure going into the transducer Install the device using a wrench on the hex flats provided Do not use a strap wrench on the body When installing the GP sensor the torque limit is 150 in lbs 16 95 Nm Do Not over tighten Overtightening metal fittings may cause a slight zero shift The use of plastic fittings typically results in no noticea...

Страница 3: ...gnal is Inaccurate SOLUTION S ConfirmtheDCsupplyvoltageis 4 20mAOutput 250OhmLoad 13to30VDC 500OhmLoad 18 to 30VDC DisconnectthesensorfromthelinetoensureNoderisorsedimentis blockingtheinletportofthetransducer Determinethattheproperoutputisbeingtransmittedbasedonthe predetermined span Measure the output of the transmitter with a handheld multimeter and compare the measured output to calculate outpu...

Страница 4: ...teel 1 4 18 NPT 800 Ω 24 VDC Formula Supply VDC 8 VDC 0 020 A 15 to 300 psig 3x FS 500 psis 3x FS 0 to 95 RH non condensing Any gas or liquid compatible with 304L Stainless Steel 150 lbs in 16 95 Nm SENSOR NON SPECIFIC INFORMATION Supple Voltage Supply Current Output Signal Accuracy1 22 C 71 6 F Thermal Error 40 to 105 C Stability 250 Hours 225 F 125 C Operating Storage Temperature Ranges Process ...