Page 6
Getting Started
Wire Table
Color
Pin
Function
BLK
1
HTR (+)
WHT
2
HTR (-)
ORG
3
DC(+)
SHIELD
4
CMN
BLU
5
Pres (+)
RED
6
Enc Temp
YEL
7
OA Temp
GRN
8
Temp Cmn
BRN
9
Zero Valve
Step 6
Wiring
Transducer Wiring
Connect the 50-foot cable assembly to the pressure transducer. One end of this
cable has flying leads to allow cable to be run through conduit.
Loosen the strain relief fitting nut on the lower right side of the monitor enclosure.
Guide the cable end through the strain relief fitting and terminate the transducer
wires to the monitor 9-pin terminal block per Figure 3. Be sure to secure each
screw after landing wire in the proper location.
Secure strain relief fitting nut.
Figure 3
Transducer Wiring
Input Power Wiring
Loosen the strain relief fitting nut located on the lower left side of the monitor
enclosure.
Guide the 24 VAC input power wires (18 AWG) through the strain relief fitting and
terminate on the green input power terminals.
Note: The power source must be capable of providing 25 VA to the monitor.
24 VAC
1
2
3
1
2
1
2
1
2
1
2
3
1
Figure 4
Input Power Wiring