Custom Set-Up
Press. Average Int --
Enter the Averaging Time in seconds between one and twenty
seconds for the average pressure calculation. Factory default is 2 seconds.
Use Fan Interlock? --
Select either NO (OFF) or YES (ON) to activate or deactivate
the fan interlock. The Fan Interlock Function is used to interlock the action of the
monitor to the running of the fan. The default setting is OFF, meaning the feature is
not active. If the Fan Interlock Function is ON, the low CFM airflow alarm is
deactivated any time the digital input function reports that the fan is OFF. When the
fan is ON the alarm is active. The reporting of diagnostic alarms is not inhibited by
fan run status. Fan status is provided on the HOME display if this feature is
activated.
Balancers Adj Fact --
The Balancers Adj Fact (BAF) allows the Balancer to adjust
the readings determined by the monitor, to those observed by the Balancer. Enter
the BAF as a percentage of monitor reading. For example; if the monitor indicates
the flow 1000 CFM and the Balancer indicates the flow is 900 CFM, the BAF is
1000/900 = 90%. Factory default is 100%.
Password Change --
To change the password, enter new four-digit number. The
factory default is 1234.
Auto-Zero Interval --
Enter the Auto-Zero Interval in minutes between five and sixty
minutes. Factory default is 30 minutes.
Encl Temp Set Pt --
Enter the Transducer Enclosure Temperature Set Point in
degrees F. This value should be only a couple of degrees greater than the
maximum outdoor air temperature. Factory default is 100 degrees F.
OA Temp Sensor Bias --
Allows the Balancer to adjust the monitor outside air
temperature readings to those observed by the Balancer. Enter the offset desired in
degrees F. Factory default is 0.
Transducer Zero --
Sets the monitor Zero range in “wc corresponding to the
transducer 4mA output. Factory default is 0.00 “wc.
Transducer FS --
Sets the monitor Full Scale range in “wc corresponding to the
transducer 20mA output.
Factory default is 0.25”wc.