Packaged Rooftop Ventilator
6
Installation
Typical Unit Weights and Dimensions
Unit Size
ACS
CC End OA End
*NA
from
Unit
**NA
from
CS
***NA
from
Vest
XRV-25
40
42
42
24
18
30
XRV-45
36
58
42
24
18
30
XRV-70
36
52
58
24
18
30
All dimensions are shown in inches.
*NA from Unit = no condensing section or piping vestibule
**NA from CS = condensing section
***NA from Vest = piping vestibule
Clearance
ACS
CC End
Clearance
OA End
NA
ACS = Access
CC = Control Center
NA = Non-Access
OA = Outdoor Air Weatherhood
Service Clearances
Component Access
1
Optional Inverter Compressor
2
Optional Compressor/Electrical
3
Optional Gas Furnace/Optional Electric Heater
4
Electrical
5
Supply Blower
6
Coil
7
Filters
Unit
Size
Nominal
tonnage
(tons)
Height
(H)
Width
(W)
Length
(L)
Intake
(A)
Condensing
Section
(B)
Nominal
weight
(lbs)
Outdoor
Intake
Supply
Discharge
Return
Intake
Exhaust
Discharge
XRV-25
5-15
59.3
52.5
98.6
22.1
30.1
2,700
End
Bottom
or
Side
Bottom,
End**
or
Side*
End+
or
Side*
XRV-45
15-30
72.5
68.2
109
27.7
30.1
4,500
XRV-70
20-45
90
68
156
22/27^
30
6,400
All dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat, largest indirect-gas
fired furnace, and all dampers. Actual weights will vary based on the unit configuration.
* Only available with powered exhaust ** Only available without barometric relief
+Only available with barometric relief ^ Above 12,000 cfm
L
W
H
B
A
1
2
3
4
5
6
7