Accurex XMPX Series Скачать руководство пользователя страница 36

Units with Packaged DX

  1.  Evaporator Coil Maintenance 

 

Check for cleanliness - clean if required

  2.  Condenser Coil Maintenance 

 

Check for cleanliness - clean if required

 3.  Condensate Drain 

 

Inspect and clean - refill with water

  4.  Condensing Fan Blades and Motors 

 

Check for cleanliness 

 

Check all fasteners for tightness 

 

Check for fatigue, corrosion and wear

Maintenance Procedures:
Lubrication

Check all moving components for proper lubrication. 
Apply lubricant where required. Any components 
showing excessive wear should be replaced to 
maintain the integrity of the unit and ensure proper 
operation.

Dampers

Check all dampers to ensure they open and close 
properly and without binding. Backdraft dampers can 
be checked by hand to determine if blades open and 
close freely. Apply power to motorized dampers to 
ensure the actuator opens and closes the damper as 
designed.

Fan Belts

Belts must be checked on a regular basis for wear, 
tension, alignment and dirt accumulation. Premature 
or frequent belt failures can be caused by improper 
belt tension (either too loose or too tight) or 
misaligned sheaves. Abnormally high belt tension or 
drive misalignment will cause excessive bearing loads 
and may result in failure of the fan and / or motor 
bearings. Conversely, loose belts will cause squealing 
on start-up, excessive belt flutter, slippage and 
overheated sheaves. Both loose and tight belts can 
cause fan vibration.

Routine Maintenance

DANGER

Electric shock hazard. Can cause injury or death. 
Before attempting to perform any service or 
maintenance, turn the electrical power to the unit 
to OFF at disconnect switch(es). Unit may have 
multiple power supplies. 

CAUTION

Use caution when removing access panels or other 
unit components, especially while standing on a 
ladder or other potentially unsteady base. Access 
panels and unit components can be heavy and 
serious injury may occur.

This unit requires minimal maintenance to operate 
properly. To ensure proper operation and longevity, the 
following items should be completed. The items in this 
list assume a relatively clean air environment, and may 
require attention more frequently in a dusty or dirty 
area. If this unit contains an indirect gas-fired heater, 
refer to the Installation, Operation and Maintenance 
manual provided with the unit for maintenance 
purposes. A Certified Technician should complete all 
refrigerant systems checks.

Maintenance Frequency:

Monthly

 1.  External Filter 

 

Check for cleanliness – clean if required

 2.  Internal Filters 

 

Check for cleanliness – replace if required

  3.  Condensate Drain (if applicable) 

 

Inspect and clean – refill with water

 4.  Bearings 

 

 Lubricate per the schedule in the Fan Bearings 
section

Semi-Annually

 1.  Fan Belts 

 

Check for wear, tension, alignment

  2.  Check pulleys, bearings and motor for wear
 3.  Bearings 

 

 Lubricate per the schedule in the Fan Bearings 
section

Annually

It is recommended that the annual inspection and 
maintenance occur at the start of the cooling season. 
After completing the checklist, follow the unit start-
up checklist provided in the manual to ensure the 
refrigeration system operates in the intended matter.
 1.  Lubrication 

 

Apply lubrication where required

 2.  Dampers 

 

Check for unobstructed operation

 3.  Motors 

 

Check for cleanliness

 4.  Fan Belts 

 

Check for wear, tension, alignment

  5.  Blower Wheel & Fasteners 

 

Check for wear, tension, alignment 

 

Check all fasteners for tightness 

 

Check for fatigue, corrosion, wear

 6.  Bearings 

 

Lubricate per the schedule in the Fan Bearings 

section

 7.  Door Seal 

 

Check if intact and pliable

 8.  Wiring Connections 

 

Check all connections for tightness

 9.  Cabinet 

 

Check entire cabinet—inside and out—for dirt 

buildup or corrosion. Remove accumulated dirt, 
remove any surface corrosion and coat the area 
with appropriate finish.

36

Model MPX Make-Up Air Unit

Model XMPX Make-Up Air Unit

Содержание XMPX Series

Страница 1: ...r seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Elect...

Страница 2: ...ed to be taken to prevent deterioration of the unit during storage The user assumes responsibility of the unit and accessories during storage The manufacturer will not be responsible for damage during...

Страница 3: ...Center Components DDC Control Package 12 Digital Scroll Compressor Controller 12 Fan Proving Switch 12 Variable Frequency Drives VFD 13 Phase Monitor 13 Typical Wiring Diagram 14 15 Controller Sequenc...

Страница 4: ...Operation and Maintenance manuals for additional information Plenum and Plug Indirect Gas Fired Furnace Model PVF PCO3 Controller MPX Subassemblies Blower Each unit has just one backward curved blowe...

Страница 5: ...ATER 4 INCH FILTERS I H MPX H34 Unit Size Dimensions MPX H14 MPX H24 MPX H34 MPX H34 Furnaces Single Furnace Double Furnace A 54 3 67 2 72 2 76 2 B 86 6 96 7 97 7 97 7 C 34 0 36 4 33 2 33 2 D 48 1 58...

Страница 6: ...mage from occurring to the refrigerant system This unit contains a system that is pressurized with refrigerant and if it is damaged the refrigerant could leak into the atmosphere or cause bodily harm...

Страница 7: ...be level Shim as required to level 3 Install Ductwork Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines Duct adapter provided to support ducts prior to setting the...

Страница 8: ...rovided with the P trap If local and area building codes permit the condensate may be drained from the P trap onto the roof but a drip pad should be provided beneath the outlet If local and area codes...

Страница 9: ...o overheat and eventually fail Maximum allowable imbalance is 2 To determine voltage imbalance use recorded voltage measurements in this formula Low Voltage Controller Circuitry Manufacturer recommend...

Страница 10: ...e Air Temperature Sensor All units are supplied with a Discharge Air Temperature Sensor that is to be eld installed prior to unit start up The sensor is to be installed at least three duct diameters d...

Страница 11: ...use Blocks 10 Step Down Transformers number varies Low Voltage Side 11 DDC Controller 12 Relays 13 Fan Proving Switch Dirty Filter Switch on side wall 14 Low Voltage Terminal Strip 15 Hot Gas Reheat C...

Страница 12: ...ch The unit uses a pressure switch to prove fan operation before operating any heating or cooling sequence It does this by verifying a difference in air pressure on both sides of the air supply fan Wh...

Страница 13: ...ed sensors and controlling devices such as CO2 sensors dehumidistats or pressure sensors Refer to the VFD manufacturer s information and unit speci c wiring diagram supplied with the unit For addition...

Страница 14: ...R R7 21 24 12 FPS NO C 90 NO3 OAI OAD ACC W BL Y PK Y BL W PK BL R 111 112 SUPPLY FAN M MAIN POWER TO UNIT GROUND L1 L2 L3 DB1 DS1 Y Y PM T1 T2 T3 PM C OUT DL1 4 D1 S4 S6 Y 1 2 ST1 O L 95 96 ST1 A2 A...

Страница 15: ...RESSOR RELAY CIRCUIT B R7 COMPRESSOR INTERLOCK RELAY CIRCUIT A R8 COMPRESSOR INTERLOCK RELAY CIRCUIT B RBV REHEAT VALVE CONDENSER RH HEAT RELAY RHV REHEAT VALVE HOT GAS REHEAT S1 EXHAUST SWITCH S3 SUP...

Страница 16: ...ehumidi cation Sequence The cooling is controlled to maintain the cooling coil set point The dehumidi cation sequence will be locked out when the OA is less than 10 F above the cold coil set point The...

Страница 17: ...the proving switch on the supply air blower and displays an alarm in case of blower failure DX Alarm The DDC monitors the refrigerant pressure and shuts off the refrigeration circuit in the case of hi...

Страница 18: ...to enable or disable speci c functions of the unit A unit speci c wiring diagram is included with each panel If speci ed by the owner the remote panel may have a Remote Interface factory installed ins...

Страница 19: ...Coil M 1 2 3 4 13 5 12 9 11 13 10 8 13 14 7 15 6 Service Valve for Subcooling Gauge High Side Pressure Drop Circuit A Pressure Port for Troubleshooting Valve Service Valve for Superheat and Low Side P...

Страница 20: ...le but excessive bubbles may indicate improper charge or a leak in the system A green dot means that moisture is below a safe operation level in the refrigerant while a yellow dot indicates moisture h...

Страница 21: ...n system is excessive cycling on and off The digital scroll compressor eliminates excessive cycling by allowing the compressor to continue to run but internal compression is eliminated in brief cycles...

Страница 22: ...Once the call for cooling exceeds 70 then the digital scroll will begin running again in conjunction with the xed scroll compressor see below System Start Up During unit start up amperage draw readin...

Страница 23: ...l mode during start up Use necessary precautions to avoid injury All data must be collected while the unit is running In order to measure volts and amps the control center door must be open and the un...

Страница 24: ...e Yes No If bubbles are visible in sight glass stop the start up process Refrigerant charge may not be adequate Consult factory Color of Center Dot Green Yellow Hot Gas Bypass Operational Yes No Not p...

Страница 25: ...which may cause personal injury or failure of the following components Fan Shaft Bearings Motor Fan Wheel Belt Tighten all fasteners and set screws securely and realign drive pulleys after adjustment...

Страница 26: ...cess doors open or without proper ductwork in place as the fan motors will overload Vibration Excessive vibration may be experienced during initial start up Left unchecked excessive vibration can caus...

Страница 27: ...low prior to contacting the factory please determine the following information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with S...

Страница 28: ...FD to regulate fan speed in response to various optional sensors such as dehumidistats pressure sensors or CO2 sensors These may be factory installed or they may be provided and installed by the owner...

Страница 29: ...t Check motor wiring Check motor nameplate versus supplied voltage Motor horsepower too low See speci cations and catalog for fan curves to determine if horsepower is suf cient Shorted windings in mot...

Страница 30: ...a 1 64 inch de ection per foot of span between sheaves Worn belt Replace Motor base or blower loose Tighten mounting bolts Bearing and drive misaligned Realign Noise being transmitted by duct Make sur...

Страница 31: ...ine voltage Check line voltage If more than 10 from compressor marking correcting is necessary Compressor motor protector open Motor thermal protector automatically resets Allow time 2 hours for compr...

Страница 32: ...erload If compressor is hot allow compressor to cool for two hours Recheck for open circuit Improper refrigerant charge Check subcooling Improperly wired Review wiring schematics Loose wiring Check al...

Страница 33: ...ove non condensable from system Dirty condenser coil Clean condenser coil Condenser fan not running or running backwards Check electrical circuit and fuse Check fan cycling controls High load conditio...

Страница 34: ...n oversized Contact factory Compressor loses oil Refrigerant leak Check system for leaks Repair leaks and add refrigerant Short cycling Check low pressure control settings Refrigerant ood back Check t...

Страница 35: ...air ow Check air ow check lters check drive for loose parts or belts Malfunctioning or defective expansion valve Check bulb of thermal expansion valve Frost on evaporator coil Hot gas bypass valve not...

Страница 36: ...ess panels and unit components can be heavy and serious injury may occur This unit requires minimal maintenance to operate properly To ensure proper operation and longevity the following items should...

Страница 37: ...ted and require no further lubrication under normal use Normal use being considered 20 F to 120 F and in a relatively clean environment Some bearings are relubricatable and will need to be re greased...

Страница 38: ...less may be used to clean coils with a n thickness over 0 0095 inches thick TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the ns will withstand the spray pressure For coils...

Страница 39: ...____________________________ _________________________________________________ Date __________________ Time _____________ AM PM Notes ___________________________________________ ______________________...

Страница 40: ...transportation prepaid Motors are warranted by the motor manufacturer for a period of one year Should motors furnished by Accurex prove defective during this period they should be returned to the nea...

Отзывы: