6
IO Modual
For example, if A=20, the recorded number of pulses counted by DI1
circuit of AXM-IO11 is 100 (4349H to 434aH registers), then the real
number of pulses is 20×100=2000.
The parameter setting is shown in figure 3-13.
3.3 Relay Output
Relays in IO modules can work in two different modes, one is controlling
mode, and the other is alarm mode. For controlling mode, relays can
be switched on and off directly. For alarm mode, action of relays is
controlled by whether the alarm is occurred or not.
There are two modes selection for relay output, one is latching, and the
other is pulse. For the latching mode, the relay can be used to output
two statues on or off. For the pulse mode, the output of the relay
changes from off to on for a period time Ton and then goes off. Ton can
be set from 50 to 3000ms.
Note: when relay is working in alarm mode, the default output mode is
latching mode.
1. Display of Relay State
If relay state is “ON”, it means that relay is switched on. If relay state is
“OFF”, it means that relay is switched off.
Figure 3-7 shows the states of relays read on screen.
Figure 3-1 shows the states of relays read by the utility software.
Содержание Acuvim II AXM-IO1
Страница 1: ...MetersUSA www MetersUSA com Meters MetersUSA com Ph 1847 302 7691 Fx 1847 375 9523...
Страница 2: ......
Страница 11: ...6 Chapter 2 Installation Appearance and Dimesions Installation Method Wiring of IO Modules 5...
Страница 22: ...16 IO Modual...
Страница 41: ...IO Modual 35 Figure 3 13 Parameter setting of IO modules...
Страница 42: ...36 IO Modual...
Страница 46: ...40 IO Modual Appendix B Ordering Information Type AXM IO1 AXM IO2 AXM IO3...
Страница 47: ...IO Modual 41 Appendix C Revision History Revision Date Description 1 0 20070915...
Страница 48: ...42 IO Modual...
Страница 49: ......
Страница 50: ......