Figure 3-3 data information of SOE records read by the utility software
3. Parameter Setting of Detection of Remote Signals
Take parameter setting of AXM-IO11 (AXM-IO1 module in sub address 0)
for example.
“109eH” register: this register is an unsigned integer, where bit0
determines DI1’s working mode, bit1 determines DI2’s working mode, and
so on. If the bit is “1”, then the DI circuit is set to be counter of pulses.
Otherwise, the DI circuit is set to detect remote signals. Figure 3-13
shows the parameter setting of digital input circuits.
“101bH” register: this register is an unsigned integer, it determines
that which IO module will be SOE enabled. If register is “0”, then any