IO Modual
11
Figure 2-6 schematic diagram of digital input circuit
The circuit drawing of digital input is simplified as figure 2-6. When K is
switched off, OUT is in high state. When K is switched on, OUT is in low
state.
Auxiliary power supply for the digital input is 20-250 Vad/Vdc. The max
current in the loop line is 2mA.
The wire of digital input should be chosen between AWG22~16 or 0.5~
1.3mm
2
.
Wiring of Relay Output Circuit:
There are 2 relay output circuits in AXM-IO1 and AXM-IO3 modules
respectively. The relay output circuit can work in controlling state,
or work in alarm state. When it works in controlling state, it has two
optional output modes, latching mode and pulse mode. When it works in
alarm state, it has only one latching output mode.
Relay type is mechanical Form A contact with 3A/250Vac or 3A/30Vdc. A
mediate relay is recommended in the output circuit as in figure 2-7.
Electrical
Adjuster
VCC
R
OUT
0
~
50VAC/DC
K
Dn
DC
O module
Optical
coupler
Содержание Acuvim II AXM-IO1
Страница 1: ...MetersUSA www MetersUSA com Meters MetersUSA com Ph 1847 302 7691 Fx 1847 375 9523...
Страница 2: ......
Страница 11: ...6 Chapter 2 Installation Appearance and Dimesions Installation Method Wiring of IO Modules 5...
Страница 22: ...16 IO Modual...
Страница 41: ...IO Modual 35 Figure 3 13 Parameter setting of IO modules...
Страница 42: ...36 IO Modual...
Страница 46: ...40 IO Modual Appendix B Ordering Information Type AXM IO1 AXM IO2 AXM IO3...
Страница 47: ...IO Modual 41 Appendix C Revision History Revision Date Description 1 0 20070915...
Страница 48: ...42 IO Modual...
Страница 49: ......
Страница 50: ......