54
DI Status
Use Function Code 02 to read DI status.
Address
Parameter
Range
Data Type
Property
0000H
DI1
1=ON
,
0=OFF
Bit
R
0001H
D12
1=ON
,
0=OFF
Bit
R
Table 4-17 DI Address
Relay Status
Use Function Code 01 to read Relay Status, Function Code 05 to control.
Address
Parameter
Range
Data Type
Property
0000H
DO1
1=ON
,
0=OFF
Bit
R/W
0001H
DO2
1=ON
,
0=OFF
Bit
R/W
Table 4-18 Relay Status
Note:
1. Data Type: “Bit” is 1-bit binary; “Word” is 16-bit unsigned integer; “Integer” is 16-bit signed
interger; “Float” is 32-bit floating point.
2.Read/Write: “ R ”is read only, reading DI is Function Code 02H; reading DO is Function Code 01H;
reading the other parameters is 03H; “ R/W ”is read/write, write (control) relay by Function Code 05H;
Use Function Code 10H to write system parameters.Writing into non-writable addresses is forbidden.