17
OFF (Offset)
This is a software Offset that allows the user to correct the temperature display.
See the “Probe
Calibration: Software Offset” section.
dEF (Definition)
Defines ºC/ºF and whole/tenth display.
Def Value
T'140 Setting
0
tenth ºC
1
whole ºC
2
tenth ºF
3
whole ºF
Not all settings are applicable to all options. (I-out, thermocouples)
SA (Switch Alarm)
The unit is able to monitor a door or another Open/Closed Switch input. Set this parameter to activate
this alarm.
Switch Alarm:
-1
Alarm on Closed input
0
Do not alarm
1
Alarm on Open input
See the “Switch Alarm Operation” section.