background image

Power Supply

The GPI Scaled Pulse circuit is designed to operate correctly 

when supplied with any DC voltage between about 5-30 volts, 

referenced to any of the COM terminals. The supply voltage need 

not be regulated, as long as it falls within these limits. Reverse 

polarity protection is included.
Normal  operating  current  is  about  10-15  mA,  and  will  never 

exceed 25 mA.

Do not apply AC voltage to the unit. Low voltage AC will 

not damage the unit, but may cause erratic operation.

Environmental

All electronic components in the GPI Scaled Pulse circuit are 

rated for an operating temperature range of -40° F to +185° F 

(-40° C to +85° C).
The circuit will operate correctly in humidity conditions up to 

about 95% non-condensing. As with most electronic circuits, 

exposed circuitry should not be subjected to liquid moisture.
No components of the Scaled Pulse circuit are especially sensi-

tive to shock or vibration. Ordinary back-of-truck vibration will 

not damage the unit.

When installing the GPI Scaled Pulse Module, make sure that 

all electrical connections are tight and secure.
The only user-adjustable settings are to the K-factor switches. 

On a typical flowmeter, the K-factor is usually available, either 

stamped  on  the  unit  itself  or  printed  in  the  accompanying 

documentation (if you cannot find it, please contact the meter’s 

manufacturer). Using a small straight blade screwdriver or similar 

tool, simply set the module’s K-factor switches to this number.

WARNING

OPERATION

K - F A C T O R   S W I T C H E S

X

X

X

X

X

The “

X

” markers represent the digits of the K-factor. This allows 

a K-factor range of 0000.1 to 9999.9. The switches are arranged 

and labeled as follows:

Each switch may be set to any of 10 positions (0-9). Set each so 

that the whole string of switches represents the meter’s K-factor. 

The switches do not have any mechanical stops and may be 

turned all the way around.
If the meter’s K-factor does not contain a decimal point, set the 

right-most switch to “0”.
Example:  Meter K-factor is 3555 PPG

If the meter’s K-factor has more than one decimal position, you 

must round the number so that you can set the switches with 

only one decimal position.
Example:  Meter K-factor is 5252.38 PPG

If the meter’s K-factor is less than 1000.0 PPG, you must set 

the left-most switches to “0”.
Example:  Meter K-factor is 75 PPG

645 PPG  x  1.0 = Gallon 

645

645 PPG  x  0.1 = 1/10th Gallon 

64.5

645 PPG  x  10.0 - 10 Gallons 

6450

If you need one output pulse for every 1/10th unit instead of 

every whole unit, multiply the meter’s K-factor by 0.1 and then 

enter the result on the switches.
If you need one output pulse for every 10 units, multiply the 

meter’s K-factor by 10.
Example:  Meter K-factor is 645 PPG

645 PPG  x  1.0 = Gallon, set 645

(1 Pulse Out = 1 Gallon)

645 PPG  x  0.1 = 1/10th Gallon, set 64.5

(10 Pulses Out = 1 Gallon)

645 PPG  x  10.0 - 10 Gallons, set 6450

(1 Pulse Out = 10 Gallons)

X

X

X

X

X

3

5

5

5

0

5

2

5

2

4

0

0

7

5

0

0

6

4

5

0

0

0

6

4

5

6

4

5

0

0

22

Содержание TM Series

Страница 1: ...the nozzle Installation to metal connections is not recommended Install as follows 1 Plan to install turbine with a minimum straight pipe length as follows Upstream from the turbine allow a minimum st...

Страница 2: ...Type Turbine Wetted Components Housing PVC Journal Bearings PEEK Shaft Stainless Steel Rotor and Nose Cone Acetal Washers Stainless Steel Max Working Pressure TM300 All Models 225 PSIG 73 F TM400 All...

Страница 3: ...n hazardous locations Be sure O rings and seals are kept in good repair When applying power use DC power only Disconnect external power before attaching or detaching input or output wires Installation...

Страница 4: ...Switching between different units will not corrupt the Total s contents For example in GL mode the computer totalizes 10 00 gallons if the user switches to LT mode the display will read 37 85 litres...

Страница 5: ...minemaximumpowersupplyvoltageafterdetermin ing maximum allowable voltage of all electronic devices in the system 5 WIRING CAUTION T E R M I N A L L O C A T I O N S 9V_BAT Battery 6 5V to 20V EXT_V Ext...

Страница 6: ...wer OUTPUT P U R S I G N A L O U T P U T Connect signal wire to OC_OUT terminal Connect ground wire to any COM terminal NOTE Jumper should not connect pins marked Output P U R Open Collector OUTPUT P...

Страница 7: ...006 44 To replace the battery 1 Remove the two large screws and two small screws from the battery coverplate 2 Remove the battery coverplate and gasket 3 Remove the battery and clean any corrosion fro...

Страница 8: ...100 ft 1 12 902005 9 Strain Relief 1 13 901002 87 O Ring 1 Item No No Part No Description Req d 14 906005 47 Threaded Plug 1 15 906005 48 Seal 1 16 904005 63 Screw 4 40 x 3 16 in 2 17 42100117 Jumper...

Страница 9: ...powered and provides a 4 20 mA analog output propor tional to the frequency signal for communication with PLCs and other customer equipment The 4 20 mA or 0 20 mA output is calibrated under actual flo...

Страница 10: ...ction to cor rectly wire the system The display is externally powered by the loop Determine maximum power supply voltage after determin ing maximum allowable voltage of all electronic devices in the s...

Страница 11: ...Max V 35 Customer Equipment NOTE Minimum loop power supply voltage required 8 5V Max Customer Equipment Drop Wiring IR Drop CAUTION When reassembling the faceplate make sure that the enclosure seal is...

Страница 12: ...Power Supply Typ 12 24 VDC 0 5 V Analog Input Analog In Return 0 5 V Output Local Com TM Meter NOTE 1 Loop power supply electrically isolated from customer equipment NOTE 2 Actual value of loop curre...

Страница 13: ...upt the Total s contents For example in GL mode the computer totalizes 10 00 gallons if the user switches to LT mode the display will read 37 85 litres the same volume different unit OPERATION The fie...

Страница 14: ...ght press and hold both its SET and 20 buttons Release them when the light blinks NOTE During the high and low setpoint procedure if the new settings are very different from the previous settings it i...

Страница 15: ...itu ations where sensor output frequency fluctuates or wobbles substantially The GPI 4 20 mA Out with Display offers a choice of five response time settings selectable by the unit s pushbuttons Proced...

Страница 16: ...signal input connections for intermittent open or short circuits F LOOP OUTPUT 1 Output response time setting too long Select a shorter response time setting STABLE BUT especially for fast input sign...

Страница 17: ...20 ft 1 125066 3 Cable 100 ft 1 Item No No Part No Description Req d 13 906005 47 Threaded Plug 1 14 902005 9 Strain Relief 1 15 901002 87 O Ring 1 17 120054 01 Main Circuit Assembly 1 18 904005 28 S...

Страница 18: ...feet Accuracy Performance Possible conversion error in addition to any inaccuracy of coupled flowmeter as follows Max Conversion Error Nonlinearity plus span any input loop current output 0 C to 70 C...

Страница 19: ...CE All information needed for the GA Model can be found in the GX Model sections Consult one or all of the following Important Notice 9 Safety Instructions 9 Installation 9 Wiring 10 Wiring Diagrams 1...

Страница 20: ...ironmental Avoid plumbing meter where the Scaled Pulse Module is Subject to constant exposure to water or other liquids oc casional low pressure splashing will not harm unit if cable entry points are...

Страница 21: ...mA and a maximum open circuit voltage of 60 V Be sure that you never exceed these limits NOTE Do not apply any AC voltage to this output as the internal device may be damaged The output produces a si...

Страница 22: ...de screwdriver or similar tool simply set the module s K factor switches to this number WARNING OPERATION K F A C T O R S W I T C H E S X X X X X The X markers represent the digits of the K factor Thi...

Страница 23: ...d an output pulse for every whole unit please contact the factory It is possible to supply on special order units with a K factor range of 00000 to 9999 9 i e no decimal place Check cable entry seals...

Страница 24: ...t factory C EXTRA OR ERRATIC 1 Signal picking up electronic Use shielded or shorter sensor cable OUTPUT PULSES WHEN noise USING ANY INPUT 2 Electronic failure Contact factory D EXTRA OR ERRATIC 1 Usin...

Страница 25: ...Coverplate Kit 1 2 12052101 Circuit Assembly Kit 1 3 120517 01 Adapter Kit 1 4 125066 20 Cable 20 ft 1 5 901002 82 O Ring 1 6 901002 87 Seal 2 7 902005 9 Strain Relief 2 8 904002 44 Sealing Screw 1 4...

Страница 26: ...ion in 2003 This symbol indicates that this product contains electrical and electronic equipment that may include batteries printed circuit boards liquid crystal displays or other components that may...

Страница 27: ......

Страница 28: ...fied outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has been installed or operated other than in accordance with the manufa...

Отзывы: