2  CONSTRUCTIVE FEATURES

STRUCTURE

Galvanised sheet steel structure treated with a polyester powder 

coating (Ral9002) suitable for outdoor applications, for an at-

tractive look and effective resistance to corrosive agents.

Fastening devices are made of non-oxidizable materials, or car-

bon steel that has undergone surface-passivating treatments.

The compressor compartment is completely sealed and may be 

accessed on 3 sides thanks to easy-to-remove panels that greatly 

simplify maintenance and/or inspection.

On request acoustic insulation can reduce the unit noise 

emissions

CUSTOMISED HYDRAULIC KIT

 

Ū high head pump made entirely of stainless steel, already 

configured for use with mixtures of water and ethylene gly-

col up to 35% and provided with internal thermal protection.

 

Ū Expansion vessel 

 

Ū Security valve

 

Ū Filling cock (included).

 

Ū automatic vent valve.

 

Ū Water differential pressure switch and outlet water tempera-

ture probe with anti-freeze thermostat function.

 

Ū Mechanical Y filter supplied as a standard feature on all mod-

els to protect the evaporator (included).

COOLING CIRCUIT

 

Ū Scroll compressors in tandem configuration or trio, with op-

tional acoustical insulation Frame 3 e 4). The levels of effi-

ciency, reliability and noise of such components are the state 

of the art for the scroll compressor. .

 

Ū Brazed plate heat exchangers made of stainless steel and op-

timised for use with R410a.

 

Ū Finned block condenser with 8 mm copper piping and alu-

minium fins, characterised by ample heat exchange surfaces.

 

Ū Dehydrating filter.

 

Ū Flow indicator with humidity indicator.

 

Ū Thermostatic valve with external equalisation and integrat-

ed MOP function.

 

Ū Cycle reversing valve (only MPE h)

 

Ū Check valve (MPE h)

 

Ū liquid receiver  (MPE h)

 

Ū high and low pressure switch

 

Ū Water safety valve

 

Ū Schrader valves for checks and/or maintenance

 

Ū Refrigerant pressure gauges (optional)

FAN DRIVE ASSEMBLY

Electric fan with 6/8-pole external rotor motor directly keyed to 

the axial fan, with internal thermal protection on the windings, 

complete with safety grille and dedicated supporting structure.

The fan is housed in a special compartment having a profile de-

signed to optimise ventilation.

The use of finned block heat exchangers with 8 mm diameter 

pipes reduces pressure drops on the air side, thus significantly 

improving the noise levels of the units.

The condensation control system continuously and automatical-

ly regulates the fan speed, further limiting the noise emissions 

of the unit during nighttime operation and under partial load 

conditions.

FINNED BLOCK HEAT EXCHANGER

Made of 8 mm diameter copper pipes and aluminium fins, gen-

erously sized.

The special engineering of the heat exchangers allows defrost 

cycles to be carried out at maximum speed in the models with 

heat pump operation, which brings clear benefits in terms of the 

integrated efficiency of the whole cycle.

ELECTRONIC MICROPROCESSOR CONTROL

The electronic control enables the complete control of the 

MPE

 

unit. It can be easily accessed through a polycarbonate flap with 

IP65 protection rating.

The self-adaptive logic enables the unit to operate even in 

systems where the water content is low, without the use of an 

inertial water storage reservoir. By reading the outdoor air tem-

perature, it can automatically change the setpoint to adapt it to 

the outdoor load

The basic controller comes complete with the MODBuS protocol 

and enablesan immediate connection to GaRDa networks.

Main functions:

 

Ū Control over the temperature of water entering the evapo-

rator.

 

Ū Control over the temperature of water entering the evapo-

rator. (

MPE H

)

 

Ū Control of fan speed (optional)

Содержание HPE 018

Страница 1: ...TECHNICAL MANUAL RPE 19 44 HPE 18 40 Chillers and heat pumps RPE 19 44 HPE 18 40...

Страница 2: ...ORIGINAL INSTRUCTIONS The water chillers and heat pumps comply with directive 2014 68 EC PED...

Страница 3: ...system allows the setpoint to be adjust ed automatically according to the outdoor temperature in order to reduce consumption and broaden the working temperature range The unit can also function in sy...

Страница 4: ...only MPE H Check valve MPE H Liquid receiver MPE H High and low pressure switch Water safety valve Schrader valves for checks and or maintenance Refrigerant pressure gauges optional FAN DRIVE ASSEMBLY...

Страница 5: ...advanced controller whose functions extend to LAN networks Modulation of the pump group defrost Smart Defrost Sys tem ELECTRIC CONTROL BOARD Theelectriccontrolboardisconstructedandwiredinaccordance wi...

Страница 6: ...acoustic insulation and sound blanket 8 Refrigerant pipework accessories 0 Absent M Refrigerant pressure gauges 9 Remote control Serial communication 0 Absent 2 RS485 serial board Carel Modbus protoco...

Страница 7: ...sure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Buffer tank accessory 8 9 4 Way valve MPE H 10 Thermostatic valve 11 Water safety valve 12 Liquid receiver fan hous...

Страница 8: ...ita acqua 1 1 4 femmina 3 Scarico valvola di sicurezza con portagomma 4 Alimentazione acqua 1 2 maschio rubinetto optional 5 Scarico acqua 1 2 femmina 6 Alimentazione elettrica 28 mm 7 Quadro elettric...

Страница 9: ...alvola di sicurezza con portagomma 4 Alimentazione acqua 1 2 maschio rubinetto optional 5 Scarico acqua 1 2 femmina 6 Alimentazione elettrica 37 mm 7 Quadro elettrico 8 Antivibranti 1012 1108 201 356...

Страница 10: ...0 50 50 Expansion vessel volume dm 5 5 5 Unit connections diameter 1 1 4 1 1 4 1 1 4 Height mm 1274 1274 1274 Depth mm 605 605 605 Length mm 1588 1588 1588 Sound power level 4 E dB A 71 72 72 Sound pr...

Страница 11: ...8 Unit connections diameter 1 1 4 Height mm 1451 1451 1451 1451 Depth mm 951 951 951 951 Length mm 1988 1988 1988 1988 Sound power level 4 E dB A 73 73 73 75 Sound pressure level 5 dB A 45 45 45 47 R...

Страница 12: ...50 50 50 125 Expansion vessel volume dm 5 5 5 8 Unit connections diameter 1 1 4 1 1 4 1 1 4 1 1 4 Height mm 1274 1274 1274 1451 Depth mm 605 605 605 951 Length mm 1588 1588 1588 1988 Sound power leve...

Страница 13: ...er 1 1 4 1 1 4 1 1 4 Height mm 1451 1451 1451 Depth mm 951 951 951 Length mm 1988 1988 1988 Sound power level 7 E dB A 73 73 75 Sound pressure level 8 dB A 45 45 47 Refrigerant charge kg 7 5 7 8 10 8...

Страница 14: ...coefficient of pressure drop 3 0 975 1 1 63 2 64 4 0 990 1 1 24 1 53 5 1 000 1 1 00 1 00 6 1 015 1 0 85 0 72 7 1 030 1 0 74 0 54 8 1 040 1 0 65 0 42 7 2 WATER AND GLYCOL MIXTURE Based on the minimum o...

Страница 15: ...Total sound power level weighted A 3 Sound power level measured according to ISO 9614 Sound levels RPE RPE 125 Hz 1 250 Hz 1 500 Hz 1 1000 Hz 1 2000 Hz 1 4000 Hz 1 8000 Hz 1 LwA 2 Sound power level l...

Страница 16: ...e C 8 20 22 42 Outlet water temperature C 5 16 25 531 Temperature difference on the water side C 3 8 3 8 Outdoor air temperature C 202 47 10 203 1 Value achievable only for outdoor air temperatures ab...

Страница 17: ...emperature OPZ 1 Condensing control OPZ 2 Glycol low temperature option OPZ 1 2 Condensation control glycol low temperature option EEV Electronic expansion valve STD Standard opz 1 2 EEV opz 1 2 EEV o...

Страница 18: ...ope in heat pump mode Heat pump operation within the right area of the extended operating envelope beyond standard limits can be allowed only for units equipped with condensation control or EC fans an...

Страница 19: ...l of this manual is strictly forbidden 20 MPE T76 10 2 Y FILTER PRESSURE DROPS The table below shows the pressure drops of the Y filter p as a function of the water flow rate Qw assuming an average wa...

Страница 20: ...tank this oper ation may only be carried out when the unit is disconnected from the power supply It is of fundamental importance that the incoming water supply is hooked up to the connection marked Wa...

Страница 21: ...rence of system m Charging pressure of expansion tank Maximum system water content RPE19 027 HPE 018 024 1 7 1 7 145 15 1 5 133 20 2 7 105 25 2 2 77 30 3 1 49 HPE 28 40 13 1 5 231 15 1 7 213 20 2 2 16...

Страница 22: ...rge valve 5 Pressure gauge 6 Drain 7 8 Expansion vessel 9 Security valve 10 Antifreeze electric heating 11 Hydraulic pump 12 Clapet valve 13 14 15 Differential pressure switch 16 17 18 19 Water charge...

Страница 23: ...erential pressure switch Internal and external borderline OPTIONAL IN OUT 1 4 5 10 13 14 9 6 RPE HPE evaporator and tank LEGEND 1 Evaporator 2 3 Flow switch 4 Air purge valve 5 Pressure gauge 6 Drain...

Страница 24: ...er tank 8 Expansion vessel 9 Security valve 10 Antifreeze electric heating 11 Hydraulic pump 12 Clapet valve 13 14 15 Differential pressure switch 16 17 18 19 Water charge Internal and external border...

Страница 25: ...alve with the consequent risk of tripping the safety devices 1 Utility side 2 Buffer tank 3 Mixing valve 4 Circulation pump 5 On board desuperheater 1 2 3 4 5 T 35 C The bulb of the 3 way mixer valve...

Страница 26: ...l h DP Kpa 3000 4000 5000 6000 7000 5 10 15 20 25 HPE 004 019 RPE 009 019 HPE 020 T45 RPE 019 T45 HPE 54 66 HPE 54 T76 12 3 3 Heating capacities corrective factors De Superheather heating capacities c...

Страница 27: ...not fulfilled please contact the manufacturer to check for feasibility In the design of the MPE series special care has been taken to minimise noise and vibrations transmitted to the ground Even grea...

Страница 28: ...RG66004288 09 All copying even partial of this manual is strictly forbidden 29 RPE 18 27...

Страница 29: ...30 RPE HPE 28 40...

Страница 30: ...o as to pre vent prevalent winds from interfering with the fan air flow Prevalent winds opposing the fan air flow will result in a maximum air temperature below the value indicated in the operating li...

Страница 31: ...e power supply line use H07RN F rubber flexi ble cables with section as indicated in the tables in section 16 2 Electrical data For the cable passage use sheaths and channels suitable for outdoor inst...

Страница 32: ...chosen in compliance with CEI UNEL 35024 1 standard RPE HPE 040 Maximum power input kW 22 40 Maximum current absorption A 40 Star up current A 164 Startup current with soft starter A 112 Fan motor rat...

Страница 33: ...PCD connecting cables mm AWG22 PCDS connecting cables mm 1 1 1 1 1 1 1 Safety fuse F A 25 25 32 32 32 40 40 Circuit breaker IL A 25 25 32 32 40 40 50 1 The shown section is to be considered as the mi...

Страница 34: ...P PE E IG PCD remote control panel electrical connection diagram PCDS remote control panel electrical connection diagram NOTE On the terminal block of the electric control panel a voltage of 24V will...

Страница 35: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Отзывы: