34
»
HPE
HPE
018
020
024
028
032
035
040
Maximum power input
kW
12,50
13,60
14,50
18,30
18,90
21,80
22,40
Maximum current absorption
A
22
24
26
32
34
38
40
Star up current
A
76
105
159
134
166
162
164
Startup current with soft starter
A
51
72
110
91
114
111
112
Fan motor rated power
kW
0,14
0,14
0,14
0,32
0,32
0,32
0,32
Fan motor rated current
A
0,64
0,64
0,64
1,75
1,75
1,75
1,75
Pump motor rated power - LP pumps
kW
0,37
0,37
0,37
0,55
0,55
0,55
0,55
Pump motor rated current - LP pumps
A
2,00
2,00
2,00
3,00
3,00
3,00
3,00
Power supply
V-ph-Hz
400 - 3 - 50
Auxiliary power supply
V-ph-Hz
230 - 1 - 50
PCD connecting cables
mm²
AWG22
PCDS connecting cables
mm²
1
1
1
1
1
1
1
Safety fuse F
A
25
25
32
32
32
40
40
Circuit breaker IL
A
25
25
32
32
40
40
50
(1) The shown section is to be considered as the minimum recommended section. The cables must be chosen in compliance with CEI - UNEL 35024/1. standard.
Ū The maximum input power is the mains power that must be
available in order for the unit to work.
Ū The maximum current absorption refers to the current that
will trigger the internal safety devices of the unit. It is the
maximum current allowed in the unit This value may never
be exceeded; it must be used as a reference for determining
the size of the power supply line and the related safety de-
vices (refer to the wiring diagram supplied with the units).
Cross-section area of cables: 4 a/mm² approx.