IMPORTANT CABLING CONSIDERATIONS
During installation, protection of the cabling must always be fully considered:
•
Wherever possible, above grade cable runs should be positioned to make
them beyond normal reach within any installation.
•
For long above grade cable runs, external runs and in areas where public
contact and/or accidental damage is possible, the cabling should be
contained within protective conduit. Minimum spec: Schedule 40, 1.5” (ID:
Ø1.61”, OD: Ø1.74”).
•
Additional power cabling: Where power feeds require the use of third party
cabling, the power cores should be 14 AWG minimum.
•
Additional DMX control cabling: For initial control runs leading to the Terra
Linear run, these are recommended:
•
Indoor exposed or inside conduit above grade: Belden 9842
•
Indoor plenum: Belden 82842
•
Outdoor exposed, direct burial, or inside conduit below grade:
Belden 3107DB
•
Ensure that:
•
The mains input is derived from a suitable overload-protected supply.
•
All cable access points, plus the enclosure cover are correctly sealed.
•
All local codes are followed during planning and installation.
•
Connections are made, inspected and certified by a qualified electrician.
Schedule 40
1.5” conduit
1.5” flexible
conduit or
conduit coupler
for abutted
sleeves
Содержание Terra Linear
Страница 1: ...User guide Terra Linear...
Страница 2: ......
Страница 30: ...28 www acclaimlighting com IN GROUND SLEEVES 1ft 305mm Part TLAIGS1 4ft 1220mm Part TLAIGS4 DIMENSIONS...
Страница 31: ...29 www acclaimlighting com TERRA LINEAR 1ft 305mm...
Страница 32: ...30 www acclaimlighting com TERRA LINEAR 4ft 1220mm...
Страница 34: ...32 www acclaimlighting com AJBOX1...
Страница 36: ...www acclaimlighting com...