Page 19

AN120076.000_EN

Parameter:

P 3.4

Display mode – supply voltage

(in V)

When this parameter is selected, the supply voltage

measured is indicated.

Measurement and display are only possible with the

motor running. When the motor is shut down, the dis-

play is frozen. If the motor is started up again, the dis-

play is updated following the measurement time.

Note:

In parameters 3.1 to 3.4, the overload protec-

tion function is

disabled

.

The special display mode remains active for

about 20 min, after which the unit automati-

cally switches back to the normal display

mode.

If you wish to quit the special display mode

before the 20 min. have elapsed, you must re-

turn to the normal display mode by selecting

parameter P 9.9.

Parameter:

P 3.41

Supply voltage analysis

This parameter allows simple, rapid diagnosis of the

power supply voltage with the hoist in operation.

If the unit is in normal operation, the power supply vol-

tage is recorded for 500 ms each time main lift is activa-

ted.

After this parameter has been selected, the r.m.s. value

of the supply voltage is calculated for intervals of 50 ms

each. To switch to the value for the next interval, simply

press the Enter key.

Parameter:

P4.0

Second shut- down point

Using parameter P4.0, you can set the additional

shut- down point to any value between 0 and 100 % in

2 % steps.

After this parameter has been selected, the value sto-

red is displayed. Use the up and down keys to change

the value. To confirm the value selected, press Enter.

Safety note!

As the unit has an internal monitoring system

to detect possible relay welding, a power

supply for the activation of the shut- down

point must only be available at input EA when

outputs K21 and K22 have switched.

Parameter:

P4.1

Overload shut–down, hoist

1

The overload shut–down point is defined by this para-

meter and the value entered for parameter P 0.1.

Adjustment:

110 % of rated load capacity.

This parameter cannot be set to a value higher than 110

% of rated load capacity.

A value between 2 % and 110 % can be set.

Parameter:

P 4.2

Part–load switch

1

These parameters can be used to set shut–down

points from 0 to 100 % of rated load capacity, in steps of

2 %.

The shut- down point of the part load switch always re-

fers to the rated load capacity of the hoist.

It is only necessary to enter a value if you need to use

the part- load switch.

Parameter:

P 4.3

Currently not used

Parameter:

P 4.4

Operation on twin hoist

Parameter P4.4 is used to set the unit for special opera-

ting conditions. The parameter can be set to 0, 1 or 2.

Depending on the mode of operation, select the follo-

wing value:

Mode of operation

Unit 1

Unit 2

One hoist

0

- - -

Two parallel hoists

1

1

Operation on twin hoist

1

2

Parameter:

P 5.0

Extension of measurement time,

main lift

The parameter, which is used to extend the measure-

ment time, can only be accessed using a special code.
Adjustment:

Standard setting 300 ms.

Parameter:

P 5.01

Change sensitivity to rapid load

change

The parameter can only be accessed using a special

code. This parameter must not be used without the per-

mission of ABUS.

Parameter:

P 5.1

Display FEM group

This parameter indicates the full–load hours of the cor-

responding FEM group. It cannot be used to change

the full–load hours or the FEM group.

If this parameter is set to 0000, the load population re-

corder is not active.

FEM group

Full–load hours

1Dm

M1

100

1Cm

M2

200

1Bm

M3

400

1Am

M4

800

2m

M5

1600

3m

M6

3200

4m

M7

6300

5m

M8

12500

Parameter:

P 5.2

Load population recorder

This parameter can be used to read out the data of the

load population recorder:

1. Theoretical service life

D

2. Actual hours of use

S

3. Load spectrum factor

kmi

4. Total operating hours

Ti

5. Remaining service life

6. Starting value

Содержание LIS-SE

Страница 1: ...iven to third parties and its content must not be divulged or used for other purposes without the prior written permission of ABUS You will be liable to pay compensation for any breach of this provisi...

Страница 2: ...asurement Module 6 3 3 Load indicator Optional 6 3 3 1 Function of load indicator 7 4 Technical Data 7 4 1 Load Indicator SystemLIS SE 7 4 2 LAZ GLZ Load Indicator 7 5 Operation 8 5 1 Digital Operator...

Страница 3: ...with pole changing induction motors However it may also be used for monitoring non pole changing induction motors It is intended for in stallation in a closed housing and for use under the conditions...

Страница 4: ...ional shut down point which can be adjusted via parameter 4 0 As soon as a signal is available at input EA of the unit the lifting relays drop out when the value set in pa rameter 4 0 is exceeded The...

Страница 5: ...ut 10 years taking into consideration the group determined in accordance with FEM 9 511 Actual hours of use The actual hours of use S represent the effective use of the unit determined on the basis of...

Страница 6: ...ol inputs E1 to E4 are as follows E1 not used E2 lowering control signal E3 taring control signal E4 monitoring of fast lifting speed E5 receipt of malfunction signal from hoist 2 E6 lifting control s...

Страница 7: ...n on the pendant control is pressed H2 3 If a rotor power input of 10Watt is measured with the motor in operation the hoist is shut down and U_I is indicated on the display as long as the up or down b...

Страница 8: ...ton for about 2 se conds and then enter the appropriate CODE number see Section 5 3 If four incorrect attempts are made to enter a PIN or CODE number the menu level concerned is entirely di sabled and...

Страница 9: ...rdance with the attached wiring diagrams The ABUS LIS SE must only be installed by qualified electricians If the LIS SE is retrofitted to an existing crane inspec tion by an independent inspector may...

Страница 10: ...Page 10 Data 01 03 2016 Standard wiring diagram LIS SE with one hoist Figur 2...

Страница 11: ...Page 11 AN120076 000_EN Standard wiring diagram LIS SE with two hoists Figur 3 Katzumschaltung...

Страница 12: ...Page 12 Data 01 03 2016 Standard wiring diagram LIS SE with twin hoist Figur 4 schnell...

Страница 13: ...e manufacturer ABUS will not be liable for any injury loss or damage which may occur as a result of modifications which have not been approved or the use of products other than for the intended pur po...

Страница 14: ...a meter Range Unit Designation Remarks CodE Reading out load population recorder Menu level 1 Only available if LKS has been enabled CODE 2223 P 0 0 0 100 t Total load capacity Input not required P 0...

Страница 15: ...l 3 Only for ABUS P 9 9 Quit parameter level Quit menu level 11 Description of LIS SE parameters 0015 Operating hours are displayed on unit This display appears if 1 after the hoist has been shut down...

Страница 16: ...ing Level 2 can be accessed using CODE 1443 1 entry of measured resistance in Ohms of preci sion lift winding 2 entry of measured resistance in Ohms of main lift winding Following the entry and verifi...

Страница 17: ...rotating field power is automatically measured and recorded The power recorded is indicated on the dis play until the key is released Step 7 Pro 4 main lift setting known load Using the pendant contro...

Страница 18: ...s the unit is switched automatically back to normal operation To leave the diagnosis parameter press the Enter key for some time Parameter P 3 0 Display mode load indication in t When this parameter i...

Страница 19: ...The overload shut down point is defined by this para meter and the value entered for parameter P 0 1 Adjustment 110 of rated load capacity This parameter cannot be set to a value higher than 110 of r...

Страница 20: ...he remaining ser vice life For example this parameter is used when installing a newLIS SE on an existing system Adjustment This parameter has two levels 1 Level 1 display stored starting value 2 Level...

Страница 21: ...unit can only be unlocked by ABUS However the unit will still function correctly no 4 When you leave the menu level the current soft ware version is displayed _________________________________ 5 Tabl...

Страница 22: ...Enter the load capacity currently stored appears on display in t 3 20 e g 7 enter required value for load capacity hoist 1 in t 5 00 e g 8 Enter display flashes briefly load capacity hoist 1 is store...

Страница 23: ...on ABUS hoists or hoists with power supply voltages other than 400 V Continue with item 23 23 select motor type 0 0 0 24 Enter confirm by pressing ENTER The display on the right appears 0 00 0 25 Ente...

Страница 24: ...precision speed until it is suspended freely This function is enables for 15 min If confirmation is not given by pressing emergency shut down as described under point 33 within this time the LIS SE s...

Страница 25: ...44b Enter briefly P Nr appears on display P nr 44 Enter press until P Nr appears on display P nr 45 Enter press for about 1 sec and release 0 0 0 0 46 Enter Enter Enter PIN No from left to right After...

Страница 26: ...one phase The measurement must be made on the hoist motor using an ohmmeter or multimeter Measurements on motors with star circuits Y Measurement between neutral point and U1 resistance on one phase i...

Страница 27: ...meplate measure and enter in P1 2 2 GM 800 L 4 1 0 28 1 9 1 8 5 0 28 2 4 06 I 8 306 9743 3 GM 800 H 4 2 0 45 3 2 3 1 7 2 21 0 2 16 I 8 306 9743 4 GM 800 U 4 0 0 55 4 0 4 0 8 5 17 6 1 76 I 8 306 9743 5...

Страница 28: ...M 5000 H 3 10 2 9 18 8 12 2 34 0 3 97 0 27 IV 36 1381 9746 14 GM 6000 L 3 11 2 9 18 8 12 2 34 0 3 97 0 27 IV 36 1381 9746 15 Reserve 16 GM 7000 L 13 2 4 16 11 29 5 4 48 0 42 IV 36 1381 9746 1 motor 17...

Страница 29: ...4 7 0 677 I 8 306 9743 3 GM 800 H 4 0 0 45 3 2 5 4 12 5 7 0 72 II 16 613 9744 4 GM 800 U 4 0 0 55 4 0 6 9 14 7 5 86 0 585 II 16 613 9744 5 GM 1000 L 6 0 0 45 3 0 4 2 12 8 6 15 0 707 II 16 613 9744 6...

Страница 30: ...Remarks 13 GM 5000 H 3 0 2 9 18 8 21 1 59 1 31 0 09 V 60 2344 9747 14 GM 6000 L 3 0 2 9 18 8 21 1 59 1 31 0 09 V 60 2344 9747 15 Reserve 16 GM 7000 L 0 2 4 16 19 1 51 1 49 0 141 V 60 2344 9747 1 moto...

Страница 31: ...9 1 5 4 1 20 3 2 9 I 8 306 9743 3 GM 800 H 4 0 0 45 3 2 2 6 6 25 4 2 59 I 8 306 9743 4 GM 800 U 4 0 0 55 4 0 3 3 7 1 26 1 2 5 I 8 306 9743 5 GM 1000 L 6 0 0 45 3 0 2 6 6 2 26 8 3 07 I 8 306 9743 6 GM...

Страница 32: ...3 GM 5000 H 3 0 2 9 18 8 10 2 28 3 5 6 0 414 IV 36 1381 9746 14 GM 6000 L 3 0 2 9 18 8 10 2 28 3 5 6 0 414 IV 36 1381 9746 15 Reserve 16 GM 7000 L 0 2 4 16 9 2 24 6 6 15 0 64 IV 36 1381 9746 1 motor 1...

Страница 33: ...2 3 8 3 8 9 1 28 I 8 306 9743 3 GM 800 H 4 0 0 54 3 8 3 9 9 1 13 3 1 35 II 16 613 9744 4 GM 800 U 4 0 0 66 4 8 5 0 10 7 11 1 1 08 II 16 613 9744 5 GM 1000 L 6 0 0 54 3 6 3 9 3 11 7 1 34 II 16 613 974...

Страница 34: ...3 GM 5000 H 3 0 3 5 22 6 15 3 43 2 6 0 15 V 60 2344 9747 14 GM 6000 L 3 0 3 5 22 6 15 3 43 2 6 0 15 V 60 2344 9747 15 Reserve 16 GM 7000 L 0 2 9 19 2 11 6 31 2 79 0 268 IV 36 1381 9746 1 Motor 17 GM 7...

Страница 35: ...95 0 42 II 16 613 9744 3 GM 800 H 4 0 0 54 3 8 6 7 15 7 4 4 0 45 II 16 613 9744 4 GM 800 U 4 0 0 66 4 8 8 7 18 5 3 7 0 36 III 23 873 9745 5 GM 1000 L 6 0 0 54 3 6 5 2 16 3 88 0 44 II 16 613 9744 6 GM...

Страница 36: ...marks 13 GM 5000 H 3 0 3 5 22 6 26 5 74 0 866 0 05 VI 136 5169 14 GM 6000 L 3 0 3 5 22 6 26 5 74 0 866 0 05 VI 136 5169 15 Reserve 16 GM 7000 L 0 2 9 19 2 20 1 54 0 93 0 09 V 60 2344 9747 1 motor 17 G...

Страница 37: ...rmonized standards were used EN 954 1 Safety of machinery EN ISO 12100 1 Safety of machinery tools and plants EN ISO 12100 2 Safety of machinery Basic concepts general principles for design EN 60204 T...