Standard Output

Polarity must be observed when connecting the signal output to the 
load. The positive connection (+) is connected to terminal 7 and the 
negative (–) is connected to terminal 8. 
The standard API 7500 G has an open drain MOSFET (open col-
lector) output. This output requires a user-supplied external power 
supply and pull-up resistor unless your input device is compatible 
with this type of output. The output signal is protected to a maxi-
mum of 24 V. See wiring diagram below.

M02 Option TTL Output

The M02 TTL output option uses an internal power supply and an 
internal pull up resistor. An external power supply is not needed. 
The output amplitude can vary from 1 VDC to 12 VDC depending 
on the input impedance of your device. Maximum current drive 
capability is 10 mA.

Module Power

Check model/serial number label for module operating voltage to 
make sure it matches available power.
AC power is connected to terminals 1 and 3. 
For DC powered modules, polarity MUST be observed. Positive (+) is 
wired to terminal 1 and negative (–) is wired to terminal 3.

Output Calibration

Input and output ranges, if specified on your order, are factory 
pre-configured (at 24°C ±1°C). Top-mounted zero and span poten-
tiometers can be used should fine-tuning the output be necessary. 
Note: Perform the following calibration procedure any time switch 
settings are changed.
1.  Apply power to the module and allow a minimum 20 minute 

warm up time.

2.  Using an accurate calibration source, provide an input to the 

module equal to the minimum input required for the application.

3. Using an accurate frequency measurement device for the 

output, adjust the Zero potentiometer for the exact minimum 
output desired. The Zero control should only be adjusted when 
the input signal is at its minimum. This will produce the cor-
responding minimum output signal of 0 Hz.

4.  Set the input at maximum, and then adjust the Span pot for the 

exact maximum output desired. The Span control should only 
be adjusted when the input signal is at its maximum. This will 
produce the corresponding maximum output signal.

5.  Repeat adjustments for maximum accuracy.

Installation and Setup 

API 7500 G, API 7500 G SS

Precautions

WARNING! All wiring must be performed by a qualified electrician or 
instrumentation engineer. See diagram for terminal designations and 
wiring examples. Consult factory for assistance. 
WARNING! Avoid shock hazards! Turn signal input, output, and 
power off before connecting or disconnecting wiring, or removing 
or installing module. 

Précautions

ATTENTION! Tout le câblage doit être effectué par un électricien 
ou ingénieur en instrumentation qualifié. Voir le diagramme pour 
désignations des bornes et des exemples de câblage. Consulter 
l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal d'entrée, 
le signal de sortie et l'alimentation électrique avant de connecter ou 
de déconnecter le câblage, ou de retirer ou d'installer le module. 

I/O Range Switch Settings

It is easier to select ranges before installation. Ranges are listed 
below and the module side label lists common ranges. See the 
model/serial number label for module options, or if a custom range 
was specified.
Three rotary switches and two slide switches located on the side of 
the module are used to select input and output ranges. For ranges 
that fall between the listed ranges use the next highest setting and 
trim the output signal with the zero and span potentiometers. 
1. Set slide switch A to current "I" or voltage "V" depending  on input 

type. The input selector switch determines the input impedance 
for the module, typically 50 

 for current inputs and 1 M

 or 

greater for voltage.

2. From the table, find the rotary switch settings that match your 

input range and set Input B and Offset C.

3. From the table, find your frequency output range and set slide 

switch E to HI or LO to match your frequency output range.

4. From the table, find your frequency range and set rotary switch 

D to match your frequency output range.

Electrical Connections

Polarity must be observed for input and output wiring connections. If 
the input and/or output do not function, check wiring polarity.

Socket and Mounting

Install module in a protective panel or enclosure. Allow space around 
module for air flow. Use API 008 or API 008 FS socket. See specifica-
tions for maximum allowable socket voltages. The socket clips to a 
standard 35 mm DIN rail or can be mounted to a flat surface.

Input Wiring 

See the wiring diagrams. Polarity must be observed when connect-
ing the signal input. The API 7500 G input can be wired to provide 
power to drive a current loop. It can also be wired to a device that 
provides loop power.
Determine if your device provides power to the current loop or if the 
loop must be powered by the API module. Use a multi-meter to check 
for voltage at your device's output terminals. Typical voltage may be 
9-24 VDC if it provides power to the loop. 

API 7500 G  

Output LO

DE

API 7500 G  

Output HI

DE

 

0-100 Hz

1L

 

0-2 kHz

1H

 

0-200 Hz

2L

 

0-4 kHz

2H

 

0-300 Hz

3L

 

0-6 kHz

3H

 

0-400 Hz

4L

 

0-8 kHz

4H

 

0-500 Hz

5L

 

0-10 kHz

5H

 

0-600 Hz

6L

 

0-12 kHz

6H

 

0-700 Hz

7L

 

0-14 kHz

7H

 

0-800 Hz

8L

 

0-16 kHz

8H

 

0-900 Hz

9L

 

0-18 kHz

9H

 

0-1000 Hz

AL

 

0-20 kHz

AH

 

0-1100 Hz

BL

 

0-22 kHz

BH

 

0-1200 Hz

CL

 

0-24 kHz

CH

 

0-1300 Hz

DL

 

0-26 kHz

DH

 

0-1400 Hz

EL

 

0-28 kHz

EH

 

0-1500 Hz

FL

 

0-30 kHz

FH

API 7500 G SS 

Output LO

DE

API 7500 G SS 

Output HI

DE

 

0-1 Hz

1L

 

0-20 Hz

1H

 

0-2 Hz

2L

 

0-40 Hz

2H

 

0-3 Hz

3L

 

0-60 Hz

3H

 

0-4 Hz

4L

 

0-80 Hz

4H

 

0-5 Hz

5L

 

0-100 Hz

5H

 

0-6 Hz

6L

 

0-120 Hz

6H

 

0-7 Hz

7L

 

0-140 Hz

7H

 

0-8 Hz

8L

 

0-160 Hz

8H

 

0-9 Hz

9L

 

0-180 Hz

9H

 

0-10 Hz

AL

 

0-200 Hz

AH

 

0-11 Hz

BL

 

0-220 Hz

BH

 

0-12 Hz

CL

 

0-240 Hz

CH

 

0-13 Hz

DL

 

0-260 Hz

DH

 

0-14 Hz

EL

 

0-280 Hz

EH

 

0-15 Hz

FL

 

0-300 Hz

FH

mV Input

ABC

Volt Input

ABC

mA Input

ABC

  0-50 mV

V80

  0-1 V

V10

  0-1 mA

IC0

 0-100 mV

V90

  0-2 V

V20

  0-2 mA

I00

 0-200 mV

VA0

  0-2.5 V

V40

  0-4 mA

I10

 0-250 mV

VC0

  0-4 V

V30

  0-8 mA

I20

 0-400 mV

VB0

  1-5 V

V3D

  2-10 mA

I2D

 0-500 mV

V00

  0-5 V

V50

  0-10 mA

I40

  0-10 V

V60

  0-16 mA

I30

 

±5 V

V64

  0-20 mA

I50

  ±10 V

V74

  4-20 mA

I3D

4

C

0

8

E

2

A

6

3

F

B

7

5

9

D

1

Input

Select

A

B

C

          7500G 

4

C

0

8

E

2

A

6

3

F

B

7

5

9

D

1

4

C

0

8

E

2

A

6

3

F

B

7

5

9

D

1

LO

HI

D

E

Input

Range

Output

Range 

1

Input 

Offset

I

V

Output

Range 

2

M02 option 

TTL frequency 

output

Socket top 

view

2

1

8

7

3

4

5

6

Key down 

when 

panel 

mounting

Sourcing 

mA input

(–)

(+)

Passive mA  

Signal

4

5

R

i

Terminals 4 and 5 

provide 18 V loop 

power for a passive 

device

Voltage or  

sinking mA 

input

(–)

(+)

Voltage or 

Powered  

mA Signal

Terminals 5 and 6 are 

used for a powered 

mA input device

(–)

(+)

PLC, Display, 

Recorder w. 

Freq. Input

8

7

Power   Pull-Up 

Supply Resistor

  5 VDC 

1 k

 12 VDC 

2.2 k

 24 VDC 

3.3 k

(–)

(+)

(–)

(+)

(–)

(+)

PLC, Display, 

Recorder w. 

Freq. Input

R

i

Power 

Supply

Standard 

MOSFET  

(open collec-

tor) frequency 

output

AC or DC (–)

Module power

AC or DC 

(+)

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

BSOLUTE

 P

ROCESS

 I

NSTRUMENTS

API maintains a constant effort to upgrade and improve its products. 

Specifications are subject to change without notice. See api-usa.com for 

latest product information. Consult factory for your specific requirements.

WARNING:

 This product can expose you to chemicals includ-

ing lead and nickel, which are known to the State of California 

to cause cancer or birth defects or other reproductive harm. 

For more information go to www.P65Warnings.ca.gov

Cutout Control

This multi-turn potentiometer provides the user with a low thresh-
old adjustment. It disables output when input falls below a preset 
level. The low cutout potentiometer is adjustable from 2% to 25% of 
input range. The input signal must overcome this setting to produce 
an output from the unit.

Output Test Function

When the Test button is depressed it will drive the output with a 
known good signal that can be used as a diagnostic aid during 
initial start-up or troubleshooting. When released, the output will 
return to normal. Additionally external contacts across terminals 5 
and 6 can be used as a remote test function or manual over ride.
The Test Cal. potentiometer is factory set to approximately 50% 
output. It can be adjusted to set the test output from 2 to 100% of 
the output span. Press and hold the Test button and adjust the Test 
Cal. potentiometer for the desired output level.

Operation

The API 7500 G accepts a DC voltage or current input and provides 
an optically isolated frequency output that is linearly related to 
the input. Note the output duty cycle decreases as the frequency 
increases in the high ranges. 
The variable brightness green LoopTracker

®

 input LED provides a 

visual indication of the input level. It changes in intensity as the input 
changes from minimum to maximum. If the LED fails to illuminate, or 
change in intensity as the input changes, it may indicate a problem 
with module power, or signal input wiring.
Note that it may be difficult to see the LEDs under bright lighting 
conditions.
The red LoopTracker output LED provides a visual indication that 
the output frequency signal is functioning. It becomes brighter as 
the input and the corresponding output change from minimum to 
maximum. 
Failure to illuminate or a failure to change in intensity as the process 
changes may indicate a problem with the module power or signal 
output wiring.

To maintain full isola-

tion avoid combining 

power supplies in 

common with input, 

output, or unit power.

 * Do not make 

connections to 

unused terminals!