10
Ultra
Automatic closure
The automatic closure closes the opened door automatically
after a freely adjustable period. (Not in connection with the
partial opening function)
The automatic closure can only in connection with
additional safety features (photo cell / optosensor /
safety rail).
Setting automatic closure
• Remove the
operator hood.
• Move the door to
the OPEN end
position and, once
the required keep-
open time has been
reached, plug the
jumper into "AZ".
The door will move
to the CLOSE end
position. The keep-
open time is saved.
• Replace the operator hood.
Factory setting: 0 seconds, jumper in SL1.
Changing the direction of movement
A change in the direction of movement is required for double
doors and side/sectional doors.
Connection
• Unplug the RJ-45 with the green bridge (5).
• Press the "Program" key (2) once. The red LED (3) will
flash once.
• Press the "Pulse" key (1) five times. The red LED (3) will
flash six times.
• Press the "Program" key (2) once to store the change in
direction of movement and reset the electronic system.
Reprogramming door operator see page 9.
Soft run
* Distance travelled by the slide before the door reaches the
CLOSE end position.
Attention
: When changing over from 290 mm to 0 mm, you
cannot change immediately to 580 mm. This changeover can
only be made in steps by means of programming from 0 to
290 mm and 290 mm to 580 mm.
Restoring control system to factory setting:
• Press and hold down the "Program" key (2).
• Press and hold down the "Pulse" key (1).
• Wait at least 5 seconds before releasing both keys. This
resets the electronic system and the door operator lighting
flashes.
Note
: The radio commands programmed are retained.
Reprogram before operating the door operator again.
Safety rail / photo cell / optosensor
Function
: If the safety input is actuated (contact opened) the
operator stops and reverses as far as the OPEN end position.
If the "Automatic closure" function is also activated, following
the third successive obstruction message, the operator will
move to the OPEN end position and switch off.
Connection
: Unplug the RJ-45 with the yellow bridge (6) and
keep it in a safe place. Connect safety features using RJ-45s.
Emergency lock release
Function
: If the external safety relay is activated when the
door is moving (contact opened), the door will stop. Once the
emergency lock release contact has closed, the door operator
can be moved again with the next pulse.
Connection
: Unplug the RJ-45 with the yellow bridge (5) and
keep it in a safe place. Connect safety features using RJ-45s.
Connection must be performed only by qualified electricians.
In addition to the operator lights (40W), optional lighting of a
maximum of 60 W (no tubular fluorescent lamps or energy-
saving lamps) can be connected to terminals 15 and 16.
Soft run
close / mm*
„Progr
am
“ key (2)
„Pulse“
H key (1)
L
E
D
b
eam
indi
cato
r (3)
„Progr
am
“ key (2)
automatically reset
290
Factory setting
290 => 0
1 x
1 x
2 x
1 x
X
0 => 290
1 x
1 x
2 x
1 x
290 => 580
1 x
4 x
5 x
1 x
580 => 290
1 x
4 x
5 x
1 x
580 => 0
1 x
1 x
2 x
1 x
0 => 580
1 x
1 x
2 x
1 x
Reset
Fitting additional safety features
Optional lighting system/Warning light