51
3.4.1
Normal Mode Start-up
(1)
On the rear of UPS, switch ON the
AC Power
switch.
(2)
Close UPS Mains Input Breaker/Switch and Bypass Input Breaker if equipped.
(3)
Select
→Command→Operation→Normal Mode on LCD display.
(4)
Return to the Mimic Display. Wait for few minutes, the rectifier will have started.
(5)
Close the battery switch/fuses to connect the batteries after rectifier has been turned on.