This menu allows you to change all the parameters that

regulate the movement of the engines.

- RELEASED MECHANICS: NO: the reducer is not unlockable 

YES: the reducer is unlockable

- PAUSE TIME: Allows you to adjust the PAUSE time after 

which the automation closes automatically.

- MOVE MOTOR 1: Allows motor 1 to be moved to test the 

motor or position it in the desired position

- MOVE MOTOR 2: Allows motor 2 to be moved to test the 

motor or position it in the desired position

- PEDESTRIAN PERCENTAGE: It allows to adjust the 

PEDESTRIAN OPENING percentage

Press the [>] key until you reach the <RADIO> menu and 

then press [OK].

Press the key of the radio control that you want to insert in 

the memory as START.

Operating logic selection

Press the [>] key until you reach the <LOGIC> menu and 

then press [OK].

Select the logic you prefer:

- STEP-BY-STEP: when the barrier is closed, a START 

opens, during the opening phase, a START stops the 

barrier and another START closes, with the barrier open, a 

START closes, during the closing phase one START stops 

the barrier and an additional START opens.

- AUTOMATIC: when the gate is closed, a START opens, 

during the opening phase, a START stops the barrier and 

another START closes.

During the pause a START closes, the darkening of the 

photocells recharges the pause time, at the end of the 

pause the barrier closes automatically.

During the closing phase one START stops the barrier and 

another START opens.

- AUTOMATIC WITH ANTICIPABLE CLOSING: when the 

barrier is closed, a START opens, during the opening 

phase, a START stops the barrier and another START 

closes.

During the pause a START closes, the blackout of the 

photocell FT2 recharges the pause time, the passage in 

front of the photocell FT1 anticipates the reclosing, at the 

end of the pause the barrier closes automatically.

During the closing phase one START stops the barrier and 

another START opens.

- CONDOMINIUM: when the barrier is closed, a START 

opens, during the opening phase the STARTs are ignored.

During the pause, a START and the darkening of the 

photocells recharge the pause time, at the end of the 

pause the barrier closes automatically.

During the closing phase one START stops the barrier and 

another START opens.

- CONDOMINIUM WITH ANTICIPABLE CLOSING:

when the barrier is closed, a START opens, during the 

opening phase the STARTs are ignored. During the pause, 

a START and the darkening of the photocells recharge the 

pause time, the passage in front of the photocell FT1

anticipates the closing, at the end of the break the barrier 

closes automatically.

During the closing phase one START stops the barrier and 

another START opens.

Entering the radio code START

Run programming

Press the [>] key until you reach the [PROGRAM] menu 

and press [OK].

The display shows: GATE CLOSED?

If the barrier is in closed position press [OK], otherwise 

press [CANC],

Now press the START button on the remote control.

The motors will push against the closing stop for a few 

seconds, after which the barrier will begin to open.

Wait for the barrier to reach the fully open position.

Now the barrier restarts at full speed.

The barrier reaches the position of complete closure.

The programming is terminated.

Press [OK] to exit the programming procedure.

Press the START button again, the barrier will perform a 

small closing movement.

Now the barrier is in normal operation.

Speed Change

Press the [>] key until you reach the <POWER> menu and 

then press [OK].

Select the desired force and press [OK] again.

Change pause time

Press the [>] button until you reach the <PAUSE TIME> 

menu and then press [OK].

Use the [>] and [<] keys to change the pause time for 

which the automation remains open before closing in 

AUTOMATIC or CONDOMINIUM logic.

Press [OK]

Motors 

Advanced settings

Radio codes

Press the [>] key until you reach the [Setup Advanced] 

and then press [OK].

Now enter the password and press [OK].

Using the [RADIO] menu it is possible to program the 
following codes:
- START: START command from radio control
- STOP: STOP command from the remote control
- OPEN: command OPEN by radio control
- CLOSE: CLOSE command from the radio control
- PEDESTRIAN START: pedestrian opening command of the 
engine 1
- AUX COMMAND: commands the AUX output to be 

- DEAD MAN OPENING: the command opens the 
automation ignoring safeties (photocells) and obstacle 
detection (it is necessary to keep the button pressed for 
the entire duration of the maneuver)
- DEAD MAN CLOSING: the command closes the 
automation ignoring safety devices (photocells) and 
obstacle detection (it is necessary to keep the key pressed 
for the entire duration of the maneuver)
It is also possible to remove a single radio code or all radio 
codes.

6

Содержание POLY

Страница 1: ...POLY CONTROL UNIT ABEXO is a registered trademark property ABTECNO srl Via Cicogna 95 40068 San Lazzaro di Savena BO info abtecno com www abexo tech AUTOMATION ACCESSORIES AUTOMATIC CHAIN BARRIER ...

Страница 2: ... E F F L A M P E G G V E F F L A M P E G G Wiring schematic BLINKER MASTER LED MASTER 5 4 3 1 2 5 4 3 1 2 1 8 1 D4 R18 P2 P3 P4 P1 IC17 IC5 SLAVE MASTER M2 M1 LED Photocell opening manouvre Photocell closing manouvre NC COM 12 24V dc 12 24V RX NC COM 24V dc 24V RX 2 Password 7732 ...

Страница 3: ...ells available on request PHOTOCELLS Cable types and minimum thickness CONNECTION MOUNTING VOLTAGE 230 V AC FLASHING LIGHT OPTIONAL PHOTOCELL OPTIONAL THICKNESS Unbolt the 8 screws 7 and remove the front cover 4 the rear cover 5 and the plastic cover 6 from the column Insert the column on the base plate be careful that the screws get in the right position with the holes Secure the column to the ba...

Страница 4: ...lumn 3 Align the 4 holes B on the base with the 4 holes B on the column Fix the base to the column with the 4 M10 x 20 screws and the given nuts Tighten the screws firmly The upper module 1 has 2 M10 threaded holes A at its bottom Lean the module on the base Be sure to align the holes and then fix it with the 2 given M10X20 screws POLY RING Assemble the ring as you see in the picture and fix it to...

Страница 5: ...rogramming procedure the kits are supplied already programmed Press OK to change the timer Press OK to change the language Press OK and enter the password request it by phone or by mail to enter the advanced menu Q 1 2 2 3 Q 2 6 1 8 I N F S O K ERROR OK no error STP Stop FT1 Photocell 1 FT2 Photocell 2 OC1 Obstacle current motor 1 OC2 Obstacle current motor 2 OE1 Obstacle encoder motor 1 OE2 Obsta...

Страница 6: ...ONDOMINIUM WITH ANTICIPABLE CLOSING when the barrier is closed a START opens during the opening phase the STARTs are ignored During the pause a START and the darkening of the photocells recharge the pause time the passage in front of the photocell FT1 anticipates the closing at the end of the break the barrier closes automatically During the closing phase one START stops the barrier and another ST...

Страница 7: ...ses beyond a certain threshold value for a time T greater than the time of hysteresis By raising and lowering the threshold value differentiated for slow and fast for motor 1 and motor 2 it is possible to make the automation more or less sensitive to obstacles By raising the hysteresis time it is possible to set the control unit so that it ignores small obstacles by lowering the hysteresis value o...

Страница 8: ...nd check that during this maneuver the chain does not exceed the height of 50 cm from its position of total opening if the chain exceeds this height it is necessary to reduce the motor force 8 verification of the disconnection system of the power supply acting on the disconnection device power supply and disconnecting any buffer batteries check that all the LEDs on the control unit are turned off ...

Страница 9: ...on network Install a bipolar switch disconnector with contact opening equal to or higher than 3mm on the power supply network Verifies that upstream of the electrical system there is a good differential switch an overload protection and a grounding system During installation maintenance and repair work disconnect the power supply before touching the electrical parts The handling of the electrical ...