Ze nit h Z T S ( D) 3 0 -1 2 0 0A AT S , Q U I CK STA RT U S E R M A N UA L
Recommended Operating / Storage Temperature
Do not store the automatic transfer switch in corrosive environments above LC1 (sea
salt mist) and G1 as per ANSI/ ISA-S71.04-1985. Failure to comply with these instruc-
tions may result in product damage. Store the automatic transfer switch and related
accessories in a clean, dry location in their original packaging.
AC15
AC12
AC13
Ue/[V]
Ie/[A]
Ue/[V]
Ie/[A]
P/[W]
Ie/[A]
P/[W]
230
6
24
10
240
2
50
400
4
72
4
290
0.8
60
415
4
125
2
250
0.55
70
690
2
250
0.55
140
0.27
440
0.1
44
—
Table 10 Technical data for auxiliary contacts according to IEC 60947-5-1, for OA1G_, OA3G_
Environmental
Value
Environments category
E
EMC environment
A and B
Operating temperature (without derating)
-20... +40 °C
Operating temperature (with derating)
-25... +70 °C
Transportation and storage temperature
-40... +70 °C
Altitude (without derating)
Up to 2000 m
—
Table 11 General technical data of automatic transfer switch