ABB | SACE Tmax XT
Ekip Touch - Measurements | 2 - Ekip Measuring Measurements
113 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
2 - Ekip Measuring Measurements
List
The Measuring measurements are
Condition
Access
Page
Instantaneous voltages
Phase and line-to-line voltage measurements in real time
Instantaneous powers
Real time measurements of the active, reactive, apparent
phase and total powers
Instantaneous frequency
Measurement of the line frequency
Trip
List of trips (TRIP) due to voltage, frequency, power
protections
Min-Max-Med measurements
History of minimum, maximum and mean voltages and
powers recorded within a settable range
Peak factor
Real time measurement of the peak factor of the currents
Power factor
Real time measurement of the power factor
Energy counters
Measurement of active, reactive, apparent energy
The relative associated measurements are activated by means of the
Ekip Synchrocheck
module (page 174).
Instantaneous measurements
Instantaneous currents, available in the
Summary pages
, are real time measurements of the line-to-line and
phase voltages expressed in root-mean-square value.
Representation, measuring range and performance depend on the set rated voltage (Un).
Available in the Summary pages, the instantaneous powers are real time measurements of the phase and
total active powers.
Representation, measuring range and performance depend on the set rated voltage (Un) and on the rated
current defined by the rated size of the Trip unit (In); in addition, the reference changes on the basis of the
type of measurement:
•
Sn
for total powers (Sn = In * Un *
√
3).
•
Pn
for phase powers (Pn = In * Un /
√
3).
NOTE:
the phase powers and voltages are available with 4P and 3P + N CBs
Measurement
Monitor time
(min-max)
Normal operating
range
Accuracy of
value read
(1)
Line-to-line voltages
(6)
5 V ÷ 900 V
(9)
100 ÷ 690 V
0.5 %
(8)
Phase voltages
5 V ÷ 900 V
(9)
50 ÷ 400 V
0.5 %
(8)
Line frequency
30 ÷ 80 Hz
(2)
f -10 % ÷ f +10 %
(4)
0,1 %
(3)
Total active, reactive and
apparent power
(7)
|Pmin ÷ Pmax|
(5)
|0,3 ÷ 1,2 Sn|
2 %
(3)
Active, reactive and
apparent phase power
|Pmin ÷ Pmax|
(5)
|0,3 ÷ 1,2 Pn|
2 %
(3)
(1)
the accuracies refer to normal operating ranges, as established by IEC 61557-12
(2)
available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un > 277 V)
(3)
accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy Metering
package; if the Class 1 Power & Energy Metering package is present and for all other trip unit models, check
the indicated performance values from page 116
(4)
45 to 55 Hz with set frequency = 50 Hz; 54 to 66 Hz with f = 60 Hz
(5)
Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
(6)
the higher line-to-line voltages are also available in the Histograms, Measuring instruments and Measurement
summary pages
(7)
the higher total powers are also available in the Measuring instruments and Measurement summary pages
(8)
without transformers; 0.7 % with class 0.2 external transformers
(9)
without transformers; with transformers, multiply the min and max values for the transformer ratio between
primary and secondary voltages
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...