138
| XSERIES G5 | 2106026MNAA
Click
Send
.
Click the Calibrate icon on the PCCU toolbar (the Calibrate icon shows tools).
Click
I/O Interface
on the navigation tree.
Repeat the calibration procedure in section
11.5.2 Set the AI to the correct input signal
devices support voltage or current input signals from external devices. Before
proceeding with the calibration or restoring power to the device, make sure
To set the AI input signal mode:
Locate the AIs (XFC: J8, XRC: J23).
Figure 11-5: XRCG5 AIs and mode selector jumpers (default setting)
To set the AI to voltage mode:
To set the AI to current mode:
If calibrating on the XFC: Insert a precision resistor across the selected AI pins.
Analog input calibration (voltage mode), and section
11.5.4 Analog input calibration
Содержание XRC G5