15 Locking magnet on truck (-RLE2)
This accessory is mandatory in withdrawable
versions for UniGear ZS1 switchgear and PowerCube
modules to prevent the circuit-breaker from being
racked into the switchgear when the plug of the
auxiliary circuits is disconnected.
The plug also creates an anti-insertion lock against
different rated currents. Striker pins prevent the
plug from being plugged into the socket if the
circuit-breaker’s rated current is lower than the
rated current of the panel.
Note: a specific version for the circuit-breakers of
ZS8.4 switchgear is available on request. This
accessory is not available when the motor-operated
truck is required.
Characteristics
Un
48 - 110 ... 125 - 220 ... 250 Vdc
Un
110 ... 125 - 220 ... 250 Vac
Operation limits
in accordance with IEC/IEEE 62271-
37-013
Power ai inrush (Ps)
D.C. 250 W; A.C. = 250 VA
Continuous power (Pc)
D.C. = 5 W; A.C. = 5 VA
Inrush time
150 ms
Insulation voltage
2000 V 50 Hz (for 1 min)
16 Interlock for fixed circuit-breaker
Device for fixed circuit-breakers converted into
plug-in by the customer. Allows the customer to
create a mechanical lock that inhibits racking-out/
racking-in when the circuit-breaker is closed and
prevents the circuit-breaker from closing during
movement.
Note. The device must be requested when the order
is placed since it must be assembled in the factory.
Protections and locks
Various different mechanical and electromechanical protection devices and locks are available.
—
5. Description
20
V D4 G
I N S TA L L AT I O N A N D O P ER AT I N G I N S T R U C T I O N S