General characteristics
Insulation voltage
to VDE 0110 standards, Group C
660 V A.C.
800 V D.C.
Rated voltage
24 V ... 660 V
Test voltage
2 kV for 1 min
Maximum rated current
10 A - 50/60 Hz
Breaking capacity
Class 1 (IEC 62271-1)
Number of contacts
5
Quantity of contacts
10 / 16 / 20
Contact travel
90°
Actuating force
0.66 Nm
Resistance
<6,5 m
Ω
Operating temperature
–30 °C ... +120 °C
Operating temperature
–20 °C ... +70 °C (-30° ref.
ANSI 37.09)
Contact overtemperature
10 K
Mechanical life
30,000 mechanical
operations
Protection class
IP20
Cable section
1 mm
2
Electrical specifications (according to IEC 62271-100 class 1)
Rated voltage Un
Breaking capacity
24 V D.C. 20 ms
18.8 A
60 V D.C. 20 ms
7.4 A
110 V D.C. 20 ms
4.2 A
250 V D.C. 20 ms
1.8 A
Electrical specifications (according to IEC 60947)
Rated voltage Un
Breaking capacity
(10000 breaks)
220 V A.C.
Cos
j
= 0.70
20 A
220 V A.C.
Cos
j
= 0.45
10 A
24 V D.C.
1 ms
12 A
15 ms
9 A
50 ms
6 A
60 V D.C.
1 ms
10 A
15 ms
6 A
50 ms
4.6 A
110 V D.C.
1 ms
7 A
15 ms
4.5 A
50 ms
3.5 A
220 V D.C.
1 ms
2 A
15 ms
1.7 A
50 ms
1.5 A
250 V D.C.
1 ms
2 A
15 ms
1.4 A
50 ms
1.2 A
8 Transient contact (-BGB4)
This contact closes momentarily (for > 30 ms) upon
circuit-breaker opening by remote control or by
means of a shunt opening release.
The indication is not given when opening is manual
and local. In this case, a contact (–BGB11) is
activated by the manual pushbutton and cuts out
the closing indication of the transient contact
(-BGB4).
The transient contact is activated by the main
operating shaft, thus the indication is only provided
when the main contacts of the circuit-breaker
effectively open.