VD4 -3 6 K V CR A DLE R ETROFIT SOLUTION 

SER V I C E  I N S T R U C T I O N  M A N UA L

Specific VD4-36kV cradle retrofit 

instructions

Packing and transport

The medium voltage VD4-36kV cradle retrofit 
solution CBs are delivered firmly screwed to the 
floor of their containers or crates and must 
always be transported or stored in an upright 
position.

The circuit breaker is shipped in open condition 
and with closing spring discharged. Each piece of 
apparatus is protected by plastic cover to prevent 
any infiltration of water during the loading and 
unloading stages and to keep the dust off during 
storages.

Checking on receipt

Before carrying out any operation, 
always make sure that the operating 
mechanism spring is discharged, and 
that the apparatus is in the open 
position.

On receipt, check the status of apparatus, 
integrity of the packing and correspondence with     
name plate data (see figure 6.1) with what is 
specified in the order confirmation and in the 
accompanying shipping note.

Also make sure that all the materials described in 
the shipping notes are including in the supply.
Should any damage or irregularity be noted in the 
supply on packing, notify ABB (directly or through 
the agent or supplier) as soon as possible and
in any case within five days of receipt.

The cradle retrofit solution is only supplied with 
the accessories specified at time of ordering and 
validated in the order confirmation sent by ABB.

The accompanying documents inserted in the 
shipping packing are:
•  Instruction manual (this document)
•  Test certification for CB
•  Identification label
•  Copy of the shipping documents
•  Electric wiring diagram

Other documents which are sent prior to 
shipment of the apparatus are:
•  Order confirmation
•  Original shipping advice note
•  Any drawing or documents referring to 

specific configurations / conditions

Note: 

Always take photographs to document any 

major damage.

Handling

Before carrying out any operation, always check 
that the operating mechanism springs are 
discharged and that the apparatus is in the open 
position.
Always take great care during handling not to 
stress the insulating parts like epoxy pole 
housing of the breaker and the terminals  
of circuit breaker.

Fig 6.1

-

Содержание VD4 Series

Страница 1: ...6 gas CB HPA36 Addendum to VD4 installation operation and maintenance manual DISTRIBUTION SOLUTIONS VD4 36kV vacuum CB cradle solutions for retrofitting SF6 gas CB HPA36 Addendum to VD4 installation o...

Страница 2: ...4 36kV cradle retrofit solution makes the use of fixed VD4 type of circuit breaker For this reason most of the information contained in the VD4 instruction manual is also effective for this retrofit s...

Страница 3: ...fit solution 06 Specific VD4 36kV cradle retrofit instructions 06 Packing transport 06 Handling 07 Handling with slings 08 Handling with trolley 09 10 Description 11 12 Instruction for VD4 CB operatio...

Страница 4: ...on of cradle retrofit solutions require modification in existing VHA 36 switchgear panel However this apparatus allows further technical construction modifications at the customer s request to adapt t...

Страница 5: ...nce standard Section 5 3 EL operating mechanism Section 5 4 Fixed circuit breaker Section 5 4 1 General characteristics of fixed circuit breakers 36Kv Section 5 4 2 Type of circuit breakers available...

Страница 6: ...t all the materials described in the shipping notes are including in the supply Should any damage or irregularity be noted in the supply on packing notify ABB directly or through the agent or supplier...

Страница 7: ...ndling not to stress the insulating parts and the circuit breaker terminals Fig 7 1 Fig 7 2 Fig 7 3 In any case it is always advisable to carry out lifting using the supports figure 7 4 8 1 in positio...

Страница 8: ...ing platform can be moved up down depending on the direction of rotation of the handle Fig 8 1 In order to insert circuit breaker into the VHA 36 panel position the trolley in front of the panel lift...

Страница 9: ...ers withdrawable version The VD4 36kV cradle retrofit solution is specifically used for retrofitting SF6 gas circuit breakers HPA36 in ABB make VHA36 panels The circuit breaker is having three pole as...

Страница 10: ...SE 4 Indication for closing spring charged discharged 5 Operation counter 6 Lever for manually charging the closing spring 7 Rating plate 8 Earthing contact 9 Common truck 10 Cable stem 11 Coil suppor...

Страница 11: ...s figure 11 1 Legends of figure 11 1 1 Front cover 2 Opening push button 3 Closing push button 4 Indication for circuit breaker OPEN CLOSE 5 Indication for closing spring charged discharged 6 Operatio...

Страница 12: ...rcuit breaker closing The operation can only be carried out with the closing spring completely charged For manual closing press the push button 3 figure 11 1 When there is a shunt closing release the...

Страница 13: ...assembly after preparing it along with guide rails guide brackets and earth guides Rear bottom plate of CB compartment Top cover upper door assembly above CB compartment main door CB compartment main...

Страница 14: ...14 1 2 Fig 14 2 Legends of fig 14 1 and 14 2 1 SF6 circuit breaker HPA36 2 CB compartment door top 3 CB compartment main door 4 Bottom front door 3 4 Fig 14 4 1 2 3 1 24 pin socket 2 Emergency trip as...

Страница 15: ...plate assembly 2 Earth guide 3 LHS RHS guide rails 4 Rear bottom plate Fig 15 2 1 CB compartment top cover upper door assembly 2 VD4 36kV circuit breaker 3 CB compartment main door 4 Bottom front door...

Страница 16: ...is no danger of overheating Carry out the checks indicated in table 2 1 see page 17 CAUTION During installation of VD4 CB first time with existing panel before inserting VD4 CB inside cubicle ensure t...

Страница 17: ...correctly 4 Motor operator Supply the geared motor for spring charging at the relative rated voltage Carry out a few closing and opening operations N B Supply the undervoltage release and the locking...

Страница 18: ...s discharges or traces of surface discharges 3 Visual inspection of the operating mechanism and transmission 1 year or 5000 operations The elements must be free of any deformation Screws nuts bolts et...

Страница 19: ...Electrical diagram The standard VD4 circuit breaker electric circuit diagram is as follows VD4 electric diagram Each circuit breaker is always provided with the standard electric diagram or with a sp...

Страница 20: ...ated in the technical catalogue and always state the following Type of circuit breaker Rated voltage of the circuit breaker Rated normal current of the circuit breaker Breaking capacity of the circuit...

Страница 21: ...ension and ratings VD4 36kV vacuum circuit breaker cradle retrofit solution VD4 36kV cradle retrofit solution Ur 36kV Ir 1250A Isc 31 5kA 880 984 784 853 946 367 480 114 248 320 4 424 57 736 944 4 102...

Страница 22: ...NSTRUCTION MANUAL Overall dimension and ratings VD4 36kV vacuum circuit breaker cradle retrofit solution VD4 36kV cradle retrofit solution Ur 36kV Ir 2000A Isc 31 5kA 984 853 782 880 253 5 114 947 367...

Страница 23: ......

Страница 24: ...without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this...

Отзывы: