Preliminary operations

•  Collect all auxiliary material required for 

installation of the cradle retrofit solution

•  Clean the insulating bushings on panel side 

with clean dry cloths

 

CAUTION

Use proper personal protective 
equipment like hand gloves, helmets 
etc. while handling switchgears & 
making cable connections.

 

NOTE

When carrying out installation work, the 
regulations in the country of installation must 
be strictly complied with.
Disconnect power, then earth and short circuit 
connection before proceeding to work on the 
switchgear.

Installation of VD4-36kV cradle 
retrofit solution in VHA36 
switchgear  

The installation of VD4-36kV cradle retrofit 
solution VCB in existing switchgear type VHA 36 
requires modifications in existing switchgear 
panel. Refer below steps for installation of  
VD4-36kV cradle solution.
1.  Remove following components from existing 

VHA36 panel (refer fig 14.1, 14.2, 14.3, 14.4)
•  SF6 circuit breaker HPA36
•   CB compartment door (top) fixed with 

shock absorber

•   CB compartment main door
•   Bottom front door
•   Rear sheet of CB compartment
•   Racking mechanism assembly
•   LHS and RHS guide rails in CB compartment
•   24 pin socket and TEST/SERVICE limit 

switches along with wiring from terminal 
blocks in panel

•   Emergency trip assembly and earth guide

2.  Fix/mount following new components in 

existing VHA36 panel (refer fig 15.1, 15.2, 15.3)

•  Bottom plate assembly after preparing it 

along with guide rails, guide brackets and 
earth guides

•   Rear bottom plate of CB compartment
•  Top cover (upper door) assembly above CB 

compartment main door

•   CB compartment main door suitable for 

cradle retrofit solution VCB

•   Bottom front door
•   64 pin socket along with wiring up to 

terminal blocks in panel

Once the preparation of panel assembly is 
completed by mounting new bottom plate with 
guide rail & new front door, withdrawable  
VD4-36kV cradle retrofit solution VCB can be 
inserted in the panel with the help of CB handling 
trolley (refer fig 8.2 - Handling with trolley).

Circuit-breaker racking-in/-out must be carried 
out properly to avoid shocks which may deform 
the mechanical interlocks and the limit switches.
If operations are prevented or difficult, do not 
force them and check that the operating 
sequence is correct.

CAUTION

During installation of VD4-36kV 
cradle solution with withdrawable 
VCB, ensure that power supply to the 
panel  is completely switched off and 
there is no residual charge present 
on cubicle contact by use of proper 
earthing.

Wiring of auxiliary circuit 

The auxiliary circuits of the withdrawable  
circuit- breaker are fully cabled from the factory 
up to male connector. 

For the external connections, please refer to the 
electric diagram of the enclosure or of the 
switchgear. The female connector in the existing 
panel must be replaced with the corresponding 
female connector suitable for male connector of 
CB & cabling of the panel to be done up to the 
female connector during installation.

Installation

Содержание VD4 Series

Страница 1: ...6 gas CB HPA36 Addendum to VD4 installation operation and maintenance manual DISTRIBUTION SOLUTIONS VD4 36kV vacuum CB cradle solutions for retrofitting SF6 gas CB HPA36 Addendum to VD4 installation o...

Страница 2: ...4 36kV cradle retrofit solution makes the use of fixed VD4 type of circuit breaker For this reason most of the information contained in the VD4 instruction manual is also effective for this retrofit s...

Страница 3: ...fit solution 06 Specific VD4 36kV cradle retrofit instructions 06 Packing transport 06 Handling 07 Handling with slings 08 Handling with trolley 09 10 Description 11 12 Instruction for VD4 CB operatio...

Страница 4: ...on of cradle retrofit solutions require modification in existing VHA 36 switchgear panel However this apparatus allows further technical construction modifications at the customer s request to adapt t...

Страница 5: ...nce standard Section 5 3 EL operating mechanism Section 5 4 Fixed circuit breaker Section 5 4 1 General characteristics of fixed circuit breakers 36Kv Section 5 4 2 Type of circuit breakers available...

Страница 6: ...t all the materials described in the shipping notes are including in the supply Should any damage or irregularity be noted in the supply on packing notify ABB directly or through the agent or supplier...

Страница 7: ...ndling not to stress the insulating parts and the circuit breaker terminals Fig 7 1 Fig 7 2 Fig 7 3 In any case it is always advisable to carry out lifting using the supports figure 7 4 8 1 in positio...

Страница 8: ...ing platform can be moved up down depending on the direction of rotation of the handle Fig 8 1 In order to insert circuit breaker into the VHA 36 panel position the trolley in front of the panel lift...

Страница 9: ...ers withdrawable version The VD4 36kV cradle retrofit solution is specifically used for retrofitting SF6 gas circuit breakers HPA36 in ABB make VHA36 panels The circuit breaker is having three pole as...

Страница 10: ...SE 4 Indication for closing spring charged discharged 5 Operation counter 6 Lever for manually charging the closing spring 7 Rating plate 8 Earthing contact 9 Common truck 10 Cable stem 11 Coil suppor...

Страница 11: ...s figure 11 1 Legends of figure 11 1 1 Front cover 2 Opening push button 3 Closing push button 4 Indication for circuit breaker OPEN CLOSE 5 Indication for closing spring charged discharged 6 Operatio...

Страница 12: ...rcuit breaker closing The operation can only be carried out with the closing spring completely charged For manual closing press the push button 3 figure 11 1 When there is a shunt closing release the...

Страница 13: ...assembly after preparing it along with guide rails guide brackets and earth guides Rear bottom plate of CB compartment Top cover upper door assembly above CB compartment main door CB compartment main...

Страница 14: ...14 1 2 Fig 14 2 Legends of fig 14 1 and 14 2 1 SF6 circuit breaker HPA36 2 CB compartment door top 3 CB compartment main door 4 Bottom front door 3 4 Fig 14 4 1 2 3 1 24 pin socket 2 Emergency trip as...

Страница 15: ...plate assembly 2 Earth guide 3 LHS RHS guide rails 4 Rear bottom plate Fig 15 2 1 CB compartment top cover upper door assembly 2 VD4 36kV circuit breaker 3 CB compartment main door 4 Bottom front door...

Страница 16: ...is no danger of overheating Carry out the checks indicated in table 2 1 see page 17 CAUTION During installation of VD4 CB first time with existing panel before inserting VD4 CB inside cubicle ensure t...

Страница 17: ...correctly 4 Motor operator Supply the geared motor for spring charging at the relative rated voltage Carry out a few closing and opening operations N B Supply the undervoltage release and the locking...

Страница 18: ...s discharges or traces of surface discharges 3 Visual inspection of the operating mechanism and transmission 1 year or 5000 operations The elements must be free of any deformation Screws nuts bolts et...

Страница 19: ...Electrical diagram The standard VD4 circuit breaker electric circuit diagram is as follows VD4 electric diagram Each circuit breaker is always provided with the standard electric diagram or with a sp...

Страница 20: ...ated in the technical catalogue and always state the following Type of circuit breaker Rated voltage of the circuit breaker Rated normal current of the circuit breaker Breaking capacity of the circuit...

Страница 21: ...ension and ratings VD4 36kV vacuum circuit breaker cradle retrofit solution VD4 36kV cradle retrofit solution Ur 36kV Ir 1250A Isc 31 5kA 880 984 784 853 946 367 480 114 248 320 4 424 57 736 944 4 102...

Страница 22: ...NSTRUCTION MANUAL Overall dimension and ratings VD4 36kV vacuum circuit breaker cradle retrofit solution VD4 36kV cradle retrofit solution Ur 36kV Ir 2000A Isc 31 5kA 984 853 782 880 253 5 114 947 367...

Страница 23: ......

Страница 24: ...without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this...

Отзывы: