VA Master FAM540
METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E
… 9 Operation
… Parameterization of the device
Menu / parameter
Value range/Input type
Remark
▲
Main Menu
6
►
Pulse
width
0
Numerical
Only active if a pulse output is selected.
Pulse width
5 ms
5 ms
Min 5 ms
Max
256
ms
Back
Edit
Next
Ok
▼
▲
Main Menu
7
►
Operating
mode
0
Liquid: Qv, Qm
Gas: Qv, Qm
Gas standard: Qn, Qs
Qm = mass flow units
Qv = operating volume units
Qn, Qs = standard volume units
See also
‘Operating mode’ Menu
on page 54.
Operating mode
Fluid Qv
Fluid Qv
Fluid Qm
Back
Edit
Next
Ok
▼
▲
Main Menu
8
►
Unit
Qvol
l/s, l/m, l/h, m
3
/s, m
3
/m, m
3
/h, m
3
/d,
ft
3
/s, ft
3
/m, ft
3
/h, ft
3
/d, usgps,
usgpm, usgph, usmgd, igps, igpm,
igph, igpd, bbl/s, bbl/m, bbl/h, bbl/d
Only active if a volume unit is selected for the
operating mode.
Unit Qvol
l/h
l/h
m
3
/sec
Back
Edit
Next
Ok
▼
▲
Main Menu
9
►
Unit
Qm
5
g/s, g/m, g/h, kg/s, kg/m, kg/h,
kg/d, t/m, t/h, t/d, lb/s, lb/m, lb/h,
lb/d
Only active if a mass flow unit is selected for the
operating mode.
Unit Qm
kg/h
kg/h
m
3
/sec
Back
Edit
Next
Ok
▼
▲
Main Menu
10
►
Unit of density
1
g/ml, g/cm3, g/l, kg/l, kg/m3, lb/ft3,
lb/ugl
Density of the measuring medium
Unit of density
g/cm
3
g/cm
3
Back
Edit
Next
Ok
▼
▲
Main Menu
11
►
Standard
density
Numerical
Only active if a standard volume unit is selected
for the operating mode. The standard density
and the operating density are used to calculate
the measuring span of the device.
Standard density
0.001293
0.001293 g/cm
3
Min
0.000001
Max
0.100000
Back
Edit
Next
Ok
▼