- 76 -
000068DG
7 - Operation
• Alarm with reset at the end of the alarm signalling process (display
text “ALARM”):
The relay is activated (state: switched) whenever an error is present
(code Exxx) on the inverter; this does not apply to warnings (Warning
– code Wxxx). The alarm returns to its resting position when the alarm
signal ends, i.e. before the inverter checks the grid parameters after the
alarm state. This is because grid control state is not an alarm state but a
state of normal operation.
Alarms for which the relay is activated
E001
E002
E003
E004
E005
E006
E007
E010
E011
E012
E013
E014
E015
E016
E017
E018
E019
E020
E021
E022
E023
E026
E029
E030
E031
E032
E033
E034
E046
E049
E050
E051
E053
E054
E055
E056
E057
E058
W003
• Configurable alarm with reset at the end of the alarm signalling
process (display text “Alarm Conf.”)
The relay is activated (state: switched) whenever an error is present
(code Exxx) or a warning (code Wxxx) from those selected from the list in
the dedicated submenu. The contact returns to its resting position when
the alarm signal ends, i.e. before the inverter checks the grid after the
alarm state. This is because grid control state is not an alarm state but a
state of normal operation.
Selectable alarms for which the relay is activated
E001
E002
E003
E004
E005
E006
E007
E010
E011
E013
E014
E015
E017
E018
E019
E020
E021
E022
E023
E026
E027
E028
E029
E030
E031
E032
E033
E034
E046
E050
E051
E053
E054
E055
E056
E057
E058
W001
W002
W003
W008
W009
W011
W017
W018
W019
W021
W022
W023
W024
W025
W026
Ground fault
For both configurable relay operating modes “ALARM” and “ALA”. CONF.” the following con
-
siderations apply:
If the alarm condition is persistent, the alarm contact cyclically switches from its resting state
to its activated state.
In the presence of W003 signalling (Grid Fail – Network parameters out of tolerance), the
alarm contact switches to then reset itself at the end of the alarm signal. This means that
during the absence of grid voltage (display message “Vac Absent”) the alarm contact remains
in its resting position.
INVERTER RUN
SELECTED
ERROR/WARNING
OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR/WARNING
STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
N.C.
N.O.
Relay State: Switched
Relay State:
Idle
INVERTER RUN
ERROR OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR
STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State:
Idle
Relay State: Switched