![ABB UNO-2.0-I-OUTD Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/abb/uno-2-0-i-outd/uno-2-0-i-outd_product-manual_4189056.webp)
- 56 -
000030FG
6 - Instruments
D
isplay and keyboard
D
isplay fields and symbols description
Using the display, operating parameters for the equipment are shown.
signals, alarms, channels, voltages, etc.
The display, when in operation, behaves dynamically, allowing cyclical
display of certain information (see relevant chapter).
DC
AC
b02 b03 b04
b05
b06
b08
b09
b07
b01
b11
b12
b13
b24
b14
b15
b16
b17
b18
b19
b21
b20
b22
b10
b23
Ref. Description
b01
Indicates transmission and reception of data through the RS485 line
b02
Indicates presence of the RS485 communication line
b03
Indicates presence of the radio communication line (radio module board installed)
b04
Indicates presence and readiness of the Bluetooth communication line (NOT available)
b05
Indicates presence and readiness of the WiFi communication line (NOT available)
b06
Reports an active power derating for out-of-range input voltage or power restrictions set by the grid
manager or by the display
b07
Reports a power derating due to high internal temperature
b08
Instantaneous power placed on the grid
b09
MPPT SCAN function active
b10
Text lines to cyclically display the inverter parameters, error codes, and for menu navigation
b11
Graph of power introduced to grid (from 0 to 100%). Timescale can be set to 8/16/24 hours
b12
Displays the total energy from the inverter installation
b13
Shows the energy produced throughout the day
b14
Indicates that the PV generator voltage is greater than the inverter Vstart
b15
Input voltage (DC)
b16
Input current (DC)
b17
Indicates the DC/DC input circuit (Booster)
b18
Indicates the DC to AC conversion circuit
b19
Output voltage of phase highlighted
b20
Output current of phase highlighted. At the end of the currents display the grid frequency (Hz) is shown
b21
Connection to the grid:
Inverter not connected /
Inverter connected
b22
State of grid voltage:
Icon absent: grid voltage not present
Flashing icon: grid voltage present but outside parameters set by the standard grid
Icon present: Grid voltage present and within parameters set by the standard grid
b23
Main menu scrolling mode:
CYCLIC:
Cyclic display of the main parameters of the inverter.
LOCKED:
Display locked on the screen to be constantly monitored.
b24
Indicates the channel which refers to the values of voltage and input current displayed. In the event of
independent channels, parameters are displayed cyclically (channel 1 or 2)