2 Technical data
2.1 Electrical data
1) Up to 4000 A if coupled with other UniGear ZS1 units.
1) Height of the control cabinet is 705/900 mm.
2) Deeper units are available on request.
6
UniGear ZS1
I N S T A L L A T I O N , O P E R A T I O N A N D M A I N T E N A N C E
2.2 Resistance to internal arc faults
The fault withstand capacity is 31.5 kA for 1 s.
The switchgear units have been tested
according to IEC 62271-200 standard (Annex A,
accessibility type A, IAC classification FLR) and
also to PEHLA recommendation No.4. In
individual cases, depending on the
configuration of the switchgear panels and/or
the switchroom conditions (e.g. low ceiling
height), additional measures may be necessary
to ensure compliance with criterion 5.
IEC
12
12
28
75
50/60
...31.5
80
...31.5
...4000
630-1250
GB
12
12
42
75
50/60
...31.5
80
...31.5
...4000
630-1250
kV
kV
kV 1 min
kV
Hz
kA 3 s
kA
kA 1 s
A
A
Rated voltage
Rated insulationvoltage
Rated power frequency withstand voltage
Rated lightning impulse withstand voltage
Nominal frequency
Rated short-time withstand current
Peak curent
Internal arc withstand current
Main busbars rated current
1)
Branch connections rated current
Dimension (mm)
Weight (includes withdrawable modules)
Height
A
2200/2595
1)
610-850 kg
Width
- Feeder panel
B
500
Depth
C
2)
1310/1620
Height of the basic part of panel
D
2100
E
1495
2.3 Dimensions and weights