ENGINEERING
PRO CES S BUS (S MV)
1VLG5 00007 E
5 1
SMV delay
The SMV Max Delay parameter, found via menu path
Configuration/System
, defines how
long the receiver waits for the SMV frames before activating the ALARM output. This setting
also delays the local measurements of the receiver to keep them correctly time aligned. The
SMV Max Delay values include sampling, processing and network delay.
Figure 69: SMV Max delay setting in PCM600
ALARM activates when two or more consecutive SMV frames are lost or late. A single loss of
frame is corrected with a zero-order hold scheme, the effect on protection is considered neg-
ligible in this case and it does not activate the WARNING or ALARM outputs.
Table 5: Topology-dependent SMV max delay setting
Number
of hops
in
network
Internal
App.delay
[
μ
s]
[50Hz]
Internal
switch
delay [
μ
s]
Store and
forward
latency
[
μ
s]
Queue
latency
[
μ
s]
1)
Additional
tolerance
[
μ
s]
2)
Theoretical
max delay
[
μ
s]
Recommended
max delay
setting [
μ
s]
2
1 746
20
24
240
80
2 112
3 150
5
1 746
50
60
600
200
2 656
3 150
10
1 746
100
120
1 200
250
3 416
3 150
15
1 746
150
180
1 800
300
4 176
3 150
20
1 746
200
240
2 400
350
4 936
4 400
25
1 746
250
300
3 000
400
5 696
5 650
30
1 746
300
360
3 600
450
6 456
5 650
1)
Queue latency calculated when the port has started to send a full-sized frame (1500
bytes) before the SMV frame and the switch has been configured to prioritize SMV
2)
Additional tolerance in case of long wires or disturbance in network
Default max delay setting (3 150
µ
s) can be set for most of the communication topologies.
Special attention must be focused on HSR topology when number of hops in network should
be calculated for the worst situation (HSR ring is open).
Содержание UniGear Digital
Страница 1: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Страница 2: ......
Страница 3: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 67: ...ENGINEERING ETHERNET 1VLG5 00007 E 5 5 Figure74 Communicationmodules with multiple Ethernetconnectors ...
Страница 84: ...72 1VLG5 00007 E Figure94 VirtualLANs allocation in HSR PRP networks ...
Страница 111: ......
Страница 112: ... Visit us www abb com mediumvoltage Document Number 1VLG500007 Rev E ...