ENGINEERING
S TATIO N BUS (GO OS E)
1VLG5 00007 E
37
The data set defines what protection relay data is used in GOOSE service and sent to local
Ethernet subnetwork in a GOOSE message. The GOOSE control block links the data set and
its attributes to actual data.
GOOSE Control Block Attributes
–
APPID – unique GoID in network
•
Reserved value is ranging from
0x0000
to
0x3FFF
(Ed.1)
–
MAC address
•
Unique Multicast address per GoCB is recommended
•
The allowed multicast address ranges from
01-0C-CD-01-00-00
to
01-0C-CD-01-01-FF
–
GOOSE Control block name
–
Data set definition
–
VLAN ID
•
The default value is 0x000; it should be configured to > 0
•
Recommended values (as per IEC 61850-90-4) are ranging from
0x3E8 (1 000)
to
0x5E7
(1 511)
–
VLAN priority
•
The default value is
4
as per IEC 61850-8-1 (value range 0 …7)
–
Tmin (ms)
•
Maximum response time to data change
–
Tmax (ms)
•
Heartbeat cycle time in (the default value is 10 000 ms)
–
ConfRev
•
Its value increases when referenced data set becomes modified