11.
Spare parts and repairs
Typical spare parts:
10. Service
The following details of the motor operating device is to
be greased every 5 years, or after 1000 operations:
-
screw B-6
- gear wheels
B-3 and B-4
- lifting arm sliding surfaces B-1
- structure
slides
Grease:
ISOFLEX TOPAS NB 52
If other types of lubrication are used, they must be of
good quality, and suitable for use in the same range
of temperatures as the operation device.
When ordering spare parts, all details on the rating
plate are to be mentioned.
Spare parts
Type
Remarks
Motor
UEZM 5/U
U = Voltage
Control unit for UniSwitch
UEZJ 1-U
U = Voltage
Diode V1, V2
SK 1/16
Rectifi er V5, V6
- REC BR 3510
Limit switch. S1, S2
OYAX 13
Contactor K1, K2
- ABB BC6-30-01/U
U = Voltage
Relay K3
- RFI 40.52.9.048
U = Voltage