TZIDC
DIGITAL POSITIONER | DS/TZIDC-EN REV. G
—
… Use in potentially explosive atmospheres
… ATEX / UKEX
Type of protection Ex ec – increased safety
Ex marking
Ex marking
Marking
II 3 G Ex ec IIC T6, T4…T1 Gc
Type Examination Test
Certificate
TÜV 04 ATEX 2702 X
Certificate (UKEX)
EMA22UKEX0032X
Type
Equipment for increased safety
Device class
II 3 G
Standards
EN 60079
-
0, EN 60079
-
7
Special conditions
•
For the ‘Feedback on the actuator position using
proximity switches (Pepperl & Fuchs SJ2
-SN
)’ circuit,
measures outside of the device must be implemented to
prevent an up-scale of the rated voltage by more than
40% in the event of transient disturbances.
• It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
• Only non-flammable gases must be used for pneumatic
power supply.
• Only use suited cable entries that meet the requirements
of EN
60079
-
7
.
In the case of TZIDC, the following shall apply for safe use in
the Ex ‘ec IIC’ type of protection:
• Only devices that are suited for operation in
hazardous areas of Zone 2 and the conditions
prevailing at the place of use may be connected to
circuits in Zone
2 (manufacturer's declaration or
certificate from the test center).
Temperature Data
Device group II 3 G
Temperature class
Ambient temperature Ta
T4 to T1
−35
to
+85
°C
T6*
−35
to
+50
°C*
* When using the ‘Plug-in module for digital feedback’ in temperature
class T6, the maximum permissible ambient temperature range is
−35
to
+35
°C.
Electrical Data
In ‘Increased safety Ex ec’ type of protection only for
connection to a certified circuit for increased safety.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
(+11 /
-
12)
U = 9.7 V DC
I = 4 to 20
mA, max. 21.5
mA
Contact input
(+81 /
-
82)
U =
12
to 24 V DC
I = 4 mA
Switch output
(+83 /
-
84)
U = 11
V DC
Feedback on the
actuator position using
proximity switches,
(Pepperl & Fuchs SJ2
-SN
)
(Limit1: +51 / −52),
(Limit2: +41 /
-
42)
U= 8,2
V (Ri approx. 1
kΩ)
Plug-in module for
digital feedback
(+51 /
-
52)
(+41 /
-
42)
U = 5
to
11
V DC
Plug-in module for
analog feedback
(+31 /
-
32)
U = 10
to 30 V DC
I = 4 to 20
mA, max. 21.5
mA
Local communication
interface (LCI)
Only for connection to a programming device
using an ABB LCI
adapter (Um ≤ 30 V DC)
outside the hazardous area.
Содержание TZIDC
Страница 1: ...ABB MEASUREMENT ANALYTICS DATA SHEET TZIDC Digital positioner...
Страница 35: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 35 FM installation drawing No 901265 Page 1 of 5...
Страница 36: ...36 TZIDC DIGITAL POSITIONER DS TZIDC EN REV G Use in potentially explosive atmospheres cFMus Page 2 of 5...
Страница 37: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 37 Page 3 of 5...
Страница 38: ...38 TZIDC DIGITAL POSITIONER DS TZIDC EN REV G Use in potentially explosive atmospheres cFMus Page 4 of 5...
Страница 39: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 39 Page 5 of 5...