TZIDC

 DIGITAL POSITIONER  |  DS/TZIDC-EN REV. G 

 

  

— 

 

Brief description 

 

  

The TZIDC is an electronically configurable positioner with 
communication capabilities designed for mounting on 
pneumatic linear or rotary actuators. It features a small and 
compact design, a modular construction, and an excellent 
cost-performance ratio. 

Fully automatic determination of the control parameters and 

adaptation to the positioner allow for considerable time 
savings as well as optimum control behavior. 
 

 

Pneumatics 

 

An I/P module with subsequent pneumatic amplifier is used 
to control the pneumatic actuator. The well-proven I/P 
module proportionally converts the permanent electrical 
setpoint signal from the CPU into a pneumatic signal used to 
adjust a 3/3-way valve. 
Dosing of the air flow for pressurizing or depressurizing the 
actuator is continuously adjusted. As a result, excellent 
control results are achieved. When reaching the setpoint, the 
3/3-way valve is closed in center position to minimize the air 
consumption. 
The pneumatic system can be supplied in four versions: for 
single acting and double acting actuators and each with the 
‘fail-safe’ / ‘fail-freeze’ safety function. 
 

 

‘Fail-safe’ safety function 

 

If the electric power supply fails, the positioner output 1 is 

depressurized and the return spring in the pneumatic 
actuator moves the valve to the safe position. In case of a 
‘double-acting’ version, output 2 is additionally pressurized. 
 

 

‘Fail-freeze’ function 

 

If the electric power supply fails, the positioner Output 1 

 

(and Output

 

2 if applicable) is closed and the pneumatic 

actuator blocks the valve in the current position. If the 
compressed air supply power fails, the positioner 
depressurizes the actuator. 
 

 

  

 

 

Use 

 

The positioner has a built-in operating panel providing a 2-
line LCD indicator and 4 operating buttons for 
commissioning, configuration and monitoring during live 
operation. 
Alternatively, the appropriate configuration program can be 
used via the available communication interface. 
 

 

Communication 

 

The positioner has a local communication interface (LCI) as 

standard. Additionally, a ‘HART® communication’ option for 
communication via the 20 mA signal is available. Both 
communications are based on the HART® Protocol. 

Alternatively, HART®5 or HART®7 are

 available. 

 

 

Inputs / Outputs 

 

In addition to its input for the analog position setpoint, the 
positioner is equipped with a digital input which can be used 
to activate control system functions in the device. A digital 

output allows you to output collective messages (alarms

 / 

faults).

 

 

 

Modular design 

 

The basic model can be enhanced at any time by retrofitting 
optional equipment. 
Option modules can be installed for analog and digital 
position feedback. 
Additionally, a mechanical position indicator, proximity 
switches or 24 V microswitches are available for indicating 
the position independently of the mother board function. 
 

 

  

 

Содержание TZIDC

Страница 1: ...ABB MEASUREMENT ANALYTICS DATA SHEET TZIDC Digital positioner...

Страница 2: ...rward initialization Wide temperature range 40 to 85 C 40 to 185 F HART Communication Control Adaptive function Automatic adjustment of control parameters during operation Increased shock and vibratio...

Страница 3: ...to the safe position In case of a double acting version output 2 is additionally pressurized Fail freeze function If the electric power supply fails the positioner Output 1 and Output 2 if applicable...

Страница 4: ...nalog feedback 4 to 20 mA 0 Plug in module for digital feedback k Mechanical position indication l Feedback on the actuator position using proximity switches m Feedback on the actuator position using...

Страница 5: ...or The corresponding feedback shaft adapter has to be ordered separately Screwed pipe connections and air pipes have to be provided on site Figure 3 Mounting on rotary actuators in accordance with VDI...

Страница 6: ...tion sensor and is mounted on the linear and rotary actuator The TZIDC Remote Version is temporarily not available for the marine version Note To connect the TZIDC Remote Sensor a cable with the follo...

Страница 7: ...parameter can be set separately for each end position When the associated limit value is up scaled the function causes immediate travel of the actuator to the selected end position If the value 0 is...

Страница 8: ...caled adjustable time parameter Positioner inactive Counter limits up scaled adjustable in diagnosis While automatic commissioning is in progress the current state is continuously indicated on the int...

Страница 9: ...rotary actuators clockwise CLOCKW Besides this standard function a customized Autoadjust function is available The function is launched either via the operator s panel or HART communication LCD displ...

Страница 10: ...ters are saved in the non volatile memory directly upon download to the device and become active immediately LCI Adapter You can easily connect your positioner to a PC e g in the workshop or in the co...

Страница 11: ...range of 0 to 200 seconds separately for each direction Dead band time limit Setting range 0 to 200 seconds monitoring parameter for the control deviation until the dead band is reached From HW rev 5...

Страница 12: ...Class 3 except for natural gas variant Do not exceed the maximum output pressure of the actuator Independent of supply pressure Accessories Mounting material Attachment kit for linear actuators in ac...

Страница 13: ...signal Increasing set point 4 to 20 mA actuator position 0 to 100 Decreasing set point 20 to 4 mA actuator position 0 to 100 Characteristic curve actuator travel f set point signal Linear Equal percen...

Страница 14: ...and air supply switched on 95 annual average condensation permissible Transport and storage 75 annual average Safety Integrity Level Applies to applications with single acting and depressurizing pneum...

Страница 15: ...A radiated interference immunity 80 MHz to 6 GHz Chassis DIN EN 61000 4 3 10 V m A A conducted interference immunity 150 kHz to 80 MHz Input output signals DIN EN 61000 4 6 10 V A A supply frequency m...

Страница 16: ...r digital feedback SW2 Option module 31 32 Plug in module for analog feedback AO Option module 1 2 3 TZIDC remote sensor Only for options TZIDC Remote Sensor or TZIDC for remote position sensor Termin...

Страница 17: ...s It is not possible to combine both variants Electrical data for inputs and outputs Analog input Set point signal analog two wire technology Terminals 11 12 Nominal operating range 4 to 20 mA Split r...

Страница 18: ...ical 1 2 1 mA Direction of action Configurable logical 0 or logical 1 The module for analog feedback and the module for digital feedback have separate slots and can be used together Mechanical digital...

Страница 19: ...ire end sleeve with plastic sleeve 0 5 to 1 5 mm2 AWG21 to AWG17 Option modules Cross section Rigid flexible wires 0 14 to 1 5 mm2 AWG26 to AWG17 Flexible with wire end sleeve no plastic sleeve 0 25 t...

Страница 20: ...G Dimensions All dimensions in mm in Figure 15 Top view 1 Tap hole M8 10 mm 0 39 in deep 2 Tap hole M6 8 mm deep 0 31 in 3 Threaded hole M5 0 5 air outputs for direct mount 4 Sensor shaft shown large...

Страница 21: ...connections NPT in 18 or G Figure 17 Side view from left to right Figure 18 Mounting to linear actuators in accordance with DIN IEC 534 Dimensions A and B depend on the rotary actuator Figure 19 Moun...

Страница 22: ...IDC DIGITAL POSITIONER DS TZIDC EN REV G Dimensions Electrical data for inputs and outputs All dimensions in mm in Figure 20 Positioner DS_TZIDC_EN_G with mounted pressure gauge block and filter regul...

Страница 23: ...ection approvals in accordance with ATEX directives to internationally recognized approvals such as IECEx and additionally include country specific explosion protection approvals Explosion protection...

Страница 24: ...licable in the respective country VDE 0100 Part 540 IEC 364 5 54 Circulating currents must not be guided through the housing Make sure that the housing is properly installed and that its IP rating has...

Страница 25: ...and test devices as needed Maintenance and exchange work may be conducted by qualified specialists only i e qualified personnel in accordance with TRBS 1203 or similar Only those auxiliary components...

Страница 26: ...The device may only be operated using instrument air that is free from oil water and dust The use of flammable gas oxygen or oxygen enriched gas is not permitted High recurring charging processes in...

Страница 27: ...must always be discharged outside Only use suited cable entries that meet the requirements of EN 60079 11 Temperature Data Device group II 2 G II 3 G Temperature class Ambient temperature Ta T4 to T1...

Страница 28: ...9 7 In the case of TZIDC the following shall apply for safe use in the Ex ec IIC type of protection Only devices that are suited for operation in hazardous areas of Zone 2 and the conditions prevailin...

Страница 29: ...ere from forming The exhaust gas must always be discharged outside Only use suited cable entries that meet the requirements of EN 60079 11 Temperature Data Temperature class Ambient temperature Ta T4...

Страница 30: ...the test center It is only permissible to connect disconnect and switch live circuits during installation or maintenance or for the purpose of carrying out repairs Note It is considered very unlikely...

Страница 31: ...degrees of IP protection an interval for cleaning the equipment dust settlement has to be defined Strict care has to be taken that only such equipment is installed that complies with the types of prot...

Страница 32: ...osion hazardous area with Um 30 V DC Measures of lightning protection have to be provided by the user Special conditions for safe use of Positioners non I S Only devices which are suitable for the ope...

Страница 33: ...alified personnel only i e personnel qualified according to TRBS 1203 or similar Only such auxiliary components may be used in explosive atmospheres which meet all requirements of European and nationa...

Страница 34: ...TION OF CABLES SEE ELECTRICAL INSTALLATION INSTRUCTIONS IN THE MANUAL POUR LA S LECTION APPROPRI E DES C BLES VOIR LES INSTRUCTIONS D INSTALLATION LECTRIQUE DANS LE MANUEL If the equipment was tested...

Страница 35: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 35 FM installation drawing No 901265 Page 1 of 5...

Страница 36: ...36 TZIDC DIGITAL POSITIONER DS TZIDC EN REV G Use in potentially explosive atmospheres cFMus Page 2 of 5...

Страница 37: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 37 Page 3 of 5...

Страница 38: ...38 TZIDC DIGITAL POSITIONER DS TZIDC EN REV G Use in potentially explosive atmospheres cFMus Page 4 of 5...

Страница 39: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 39 Page 5 of 5...

Страница 40: ...a Temperature class Ambient temperature Ta T4 40 to 85 C T6 40 to 40 C When using the Plug in module for digital feedback in temperature class T6 the maximum permissible ambient temperature range is 4...

Страница 41: ...l valves see dimensional drawing 40 Remote sensor control unit 70 Input Communication Port Input 4 to 20 mA two wire with connector plug for LCI adapter 1 Input 4 to 20 mA two wire with connector plug...

Страница 42: ...digital position feedback 3 Plug in module for analog position feedback signal range 4 bis 20 mA two wire and digital position feedback 5 Optional Mechanical Kit for Digital Position Feedback Without...

Страница 43: ...Croatian MH Latvian ML Hungarian MM Estonian MO Bulgarian MP Romanian MR Slovak MS Lithuanian MU Slovenian MV SIL2 Declaration of Conformity SIL2 Declaration of Conformity CS2 Certificate of Complianc...

Страница 44: ...tem GPP Device Identification Label Stainless steel 18 5 65 mm 0 73 2 56 in MK1 Sticker 11 25 mm 0 43 0 98 in MK3 Special Option Cable Gland With cable gland ZG1 Type of position sensor Non contact se...

Страница 45: ...MPa single acting in NPT thread 7959360 TZIDC pressure gauge block single acting graphite black 2 pressure gauges 28 mm piping connections in NPT 1 x 0 to 10 bar 0 to 140 psi for supply air pressure...

Страница 46: ...Gb Ex ta lllC Da Ex i IP 68 ambient temperature 60 C to 180 C available Q2 Q3 2023 3KXE001078U0100 Mounting kit EDP300 TZIDC mounting kit for Fisher 1051 30 1052 30 7959214 EDP300 TZIDC mounting kit...

Страница 47: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 47 Trademarks HART is a registered trademark of FieldComm Group Austin Texas USA Sales Service...

Страница 48: ...notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We re...

Отзывы:

Похожие инструкции для TZIDC