![ABB TZIDC-210 Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/abb/tzidc-210/tzidc-210_operating-instructions-manual_3045393059.webp)
TZIDC-210, TZIDC-220
DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
59
Para-
meter
Display
Function
Possible parameter setting
Unit
Factory setting
P7.5
GOPULS DOWN
Go pulse, down
0 to 200
msec 0
P7.6
Y-OFS UP
Y offset, up
Y offset (up)
Y-Min to 100.0
%
40.0
P7.7
Y-OFS DN
Y offset, down
Y offset (down)
Y-Min to 100.0
%
40.0
P7.8
---
---
P7.9
TOL_BAND
Tolerance band (zone)
Tolerance band (zone)
0.3 to 10.0
%
0.8
P7.10
TEST
Test
Test
Function
---
INACTIVE
P7.11
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P8._, P9._,
P10._
P11._
FS / IP
P11.0
FAIL_POS
Save position
Safe position
ACTIVE, INACTIVE
---
INACTIVE
P11.1
FACT_SET
Factory setting
Factory setting
Function
---
---
P11.2
IP-TYP
I/P module type
Type of l/P module
NO_F_POS,F_SAFE_1,F_SAFE_2,
F_FREEZE1, F_FREEZE2
---
NO_F_POS
P11.3
EXIT
Return
Return to operating level
Function
---
---
* Activation by ABB Service only
Note
For detailed information on the parameterization of the device, consult the associated configuration and parameterization
instructions.
Содержание TZIDC-210
Страница 31: ...TZIDC 210 TZIDC 220 DIGITAL POSITIONER OI TZIDC 210 TZIDC 220 EN REV G 31 Page 2 of 5 ...
Страница 33: ...TZIDC 210 TZIDC 220 DIGITAL POSITIONER OI TZIDC 210 TZIDC 220 EN REV G 33 Page 4 of 5 ...
Страница 66: ...66 TZIDC 210 TZIDC 220 DIGITAL POSITIONER OI TZIDC 210 TZIDC 220 EN REV G Notes ...
Страница 67: ...TZIDC 210 TZIDC 220 DIGITAL POSITIONER OI TZIDC 210 TZIDC 220 EN REV G 67 Notes ...