34
TZIDC-200
DIGITAL POSITIONER | CI/TZIDC-200/C-FM-US-EN REV. B
… 8 Commissioning
… Sample parameters
4.
Changing parameter settings:
• Quickly press and release
to select
CTCLOCKW
.
5.
Switching to parameter 3.3 (Return to operating level) and
saving the new settings:
• Press and hold down
MODE
,
• additionally quickly press and release
2×,
The following is now shown in the display:
• Release
MODE
,
• Quickly press and release
to select
NV_SAVE
,
• Press
ENTER
and hold down until the countdown goes
from 3 to 0.
The new parameter setting is saved and the positioner
automatically returns to the operating level. It continues in the
operating mode that was active prior to the configuration level
being called up.
Setting the option modules
Setting the mechanical position indication
1.
Loosen the screws for the housing cover and remove it.
2.
Rotate the position indicator on the shaft to the desired
position.
3.
Attach the housing cover and screw it onto the housing.
Tighten the screws so that they are hand-tight.
4.
Attach the symbol label to mark the minimum and maximum
valve positions on the housing cover.
Note
The labels are located on the inside of the housing cover.
Setup of the feedback on the actuator position using
proximity switches
1. Loosen the screws for the housing cover and remove it.
CAUTION
Risk of injury!
The device includes slot sensors with sharp edges.
• Adjust the metal tags using a screwdriver only!
2. Set the upper and lower switching points for binary feedback
as follows:
• Select the ‘Manual Adjustment’ operating mode and move
the final control element by hand into the lower switching
position.
• Using a screwdriver, adjust the metal tag of proximity
switch 1 (lower contact) on the axis until contact is made,
i. e. just before it is inserted in the proximity switch. The
metal tag enters proximity switch 1 when the axis is
rotated clockwise (as viewed from the front).
• Move the final control element by hand into the upper
switching position.
• Using a screwdriver, adjust the metal tag of proximity
switch 2 (upper contact) on the axis until contact is made,
i. e.just before it is inserted in the proximity switch. The
metal tag enters proximity switch 2 when the axis is
rotated counter-clockwise (as viewed from the front).
3. Attach the housing cover and screw it onto the housing.
4. Tighten the screws so that they are hand-tight.