36 

TZIDC-200

 DIGITAL POSITIONER  |  CI/TZIDC-200/C-FM-US-EN REV. B 

 

 

 

… 9  Operation 

… Parameterization of the device 

 

Description of symbols 

 

Symbol 

Description 

 

Operation or access is restricted. 

 

Control loop is active.  
The symbol is displayed when the positioner is in operating 
mode 1.0 CTRL_ADP (adaptive control) or 1.1 CTRL_FIX (fixed 
control) at operating level. On the configuration level there are 
test functions for which the controller will be active as well. The 
control loop symbol will also be displayed when these functions 
are active. 

 

Manual adjustment. 
The symbol is displayed when the positioner is in operating 
mode 1.2 MANUAL (manual adjustment within the stroke range) 
or 1.3 MAN_SENS (manual adjustment within the measuring 
range) at operating level. At configuration level, manual 
adjustment is active when setting the valve range limits 
(parameter group 6 MIN_VR (min. of valve range) and 6 MAX_VR 
(max. of valve range)). The symbol will also be displayed when 
these parameters are being set. 

 

The configuration icon indicates that the positioner is at the 
configuration level. The control operation is inactive. 

 
The four operating buttons 

ENTER

MODE

 and 

 are pressed 

individually or in certain combinations according to the function 
desired. 
 

Operating button functions 

 

Control button 

Meaning 

ENTER 

•  Acknowledge message 
•  Start an action 
•  Save in the non-volatile memory 

MODE 

•  Choose operating mode (operating level) 
•  Select parameter group or parameter 

(configuration level) 

 

UP direction button 

 

DOWN direction button 

Press and hold all four 
buttons for 5 s 

Reset 

 

 

 

 

 

 

Menu levels 

 

The positioner has two operating levels. 

Operating level 

On the operating level the positioner operates in one of four 
possible operating modes (two for automatic control and 
two for manual mode). Parameters cannot be changed or 
saved on this level. 

 
Configuration level 

On this level most of the parameters of the positioner can be 
changed locally. The PC is required to change the limit values 
for the movement counter, the travel counter, and the user-
defined characteristic curve. 
On the configuration level the active operating mode is 
deactivated. The I/P module is in neutral position. The 
control operation is inactive. 

 

NOTICE 

Property damage 

During external configuration via a PC, the positioner no 
longer responds to the set point current. This may lead to 
process failures. 
•  Before any external parameterization, always move the 

actuator to the safety position and activate manual 
adjustment. 

 

 

 

Note 

For detailed information on how to parameterize device, consult 
the associated operating instructions and/or configuration and 
parameterization instructions. 

 

 

 

Содержание TZIDC-200

Страница 1: ...has an integral mount design features a modular structure and offers an outstanding price performance ratio Fully automatic determination of the control parameters and adaptation to the final control...

Страница 2: ...to HW Rev 5 0 17 Measurement and operating range from HW Rev 5 01 with optional contactless position feedback 19 Mounting on linear actuators 20 Mounting on rotary actuator 23 6 Electrical connection...

Страница 3: ...injury WARNING The signal word WARNING indicates an imminent danger Failure to observe this information may result in death or severe injury CAUTION The signal word CAUTION indicates an imminent dange...

Страница 4: ...st any kind of security breaches unauthorized access interference intrusion leakage and or theft of data or information ABB and its affiliates are not liable for damages and or losses related to such...

Страница 5: ...ion protection approvals The scope of these approvals extends over the entire EU Switzerland and special countries They range from explosion protection approvals in accordance with ATEX directives to...

Страница 6: ...at complies with the types of protection relevant to the applicable zones and categories When installing the equipment the locally applicable rules on erection have to be observed see Page 4 of 5 on p...

Страница 7: ...ea with Um 30 V DC Measures of lightning protection have to be provided by the user Special conditions for safe use of Positioners non I S Only devices which are suitable for the operation in explosio...

Страница 8: ...orks are to be carried out by qualified personnel only i e personnel qualified according to TRBS 1203 or similar Only such auxiliary components may be used in explosive atmospheres which meet all requ...

Страница 9: ...EE ELECTRICAL INSTALLATION INSTRUCTIONS IN THE MANUAL POUR LA S LECTION APPROPRI E DES C BLES VOIR LES INSTRUCTIONS D INSTALLATION LECTRIQUE DANS LE MANUEL If the equipment was tested according to the...

Страница 10: ...10 TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B 2 Use in potentially explosive atmospheres cFMus FM installation drawing No 901265 Page 1 of 5...

Страница 11: ...TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B 11 Page 2 of 5...

Страница 12: ...12 TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B 2 Use in potentially explosive atmospheres cFMus Page 3 of 5...

Страница 13: ...TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B 13 Page 4 of 5...

Страница 14: ...14 TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B Page 5 of 5...

Страница 15: ...system mode of action 3 Reaction in case of power failure 4 Additional options 5 Manufacturer address 6 IP rating 7 CE mark 8 Setpoint signal 9 Supply air pressure 0 Year of manufacture Calendar week...

Страница 16: ...erature should be between 40 to 85 C 40 to 185 F Avoid storing the device in permanent direct sunlight In principle the devices may be stored for an unlimited period However the warranty conditions st...

Страница 17: ...estoring the factory settings Note Before assembly check whether the positioner meets the control and safety requirements for the installation location actuator or final control element Refer to the S...

Страница 18: ...in the operating range is ideally 40 but at least 25 The usable span should run as symmetrically to the longitudinal axis as possible Operating range of rotary actuators The usable span is 57 to 57 wh...

Страница 19: ...he device feedback shaft 1 turns clockwise Figure 4 Measurement and operating range with contactless position feedback example for rotary actuators Devices from HW rev 5 01 can be equipped with the or...

Страница 20: ...ents of attachment kit Figure 6 Attaching a follower guide to the actuator 1 Tighten the screws so that they are hand tight 2 Attach the follower guide 1 and clamp plates 2 with screws 4 and spring wa...

Страница 21: ...1 with screws 2 and washers 3 using the relevant tap holes on the positioner housing Tighten the screws as evenly as possible to ensure subsequent linearity Align the mount bracket in the oblong hole...

Страница 22: ...r position on the position sensor Recommended range for linear actuators 40 Minimum angle 25 Note After mounting check whether the positioner is operating within the measuring range Position of actuat...

Страница 23: ...90 angle 2 Calculate the rotational direction of the actuator right or left 3 Move the part turn actuator into the home position 4 Pre adjust feedback shaft In order for the positioner to work within...

Страница 24: ...t onto the positioner Figure 16 Screwing positioner onto actuator Note After mounting check whether the operating range of the actuator matches the measurement range of the positioner refer to Measure...

Страница 25: ...is limited Before opening the housing switch off the power supply The electrical connection may only be established by authorized specialist personnel Notices on electrical connection in this instruc...

Страница 26: ...digital feedback SW1 Option module 41 42 Plug in module for digital feedback SW2 Option module 31 32 Plug in module for analog feedback AO Option module Terminal Function comments 51 52 Feedback on th...

Страница 27: ...t to 20 mA alarm level Terminals 31 32 Signal range 4 to 20 mA split ranges can be parameterized in the event of an error 20 mA alarm level Supply voltage two wire technology 24 V DC 11 to 30 V DC Cha...

Страница 28: ...by the operator in accordance with their use and application requirements The cable glands must comply with the requirements of EN 60079 1 EN 60079 7 EN 60079 11 or EN 60079 15 Especially in Ex appli...

Страница 29: ...with wire end sleeve with plastic sleeve 0 5 to 1 5 mm2 AWG21 to AWG17 Option modules Cross section Rigid flexible wires 0 14 to 1 5 mm2 AWG26 to AWG17 Flexible with wire end sleeve no plastic sleeve...

Страница 30: ...in accordance with DIN ISO 8573 1 Information on double acting actuators with spring return mechanism On double acting actuators with spring return mechanism a pressure that significantly exceeds the...

Страница 31: ...ccording to the tap holes available We recommend that you use a pipe with dimensions of 12 1 75 mm The supply air pressure required to apply the actuating force must be adjusted in line with the outpu...

Страница 32: ...or into the mechanical end position check the end positions rotational angle is displayed in degrees for high speed mode press or simultaneously Recommended rotational angle range Linear actuators 20...

Страница 33: ...ment within the measuring range 2 Check mechanical mounting in accordance with Standard automatic adjustment on page 33 and repeat the standard automatic adjustment The zero position is determined aut...

Страница 34: ...ons on the housing cover Note The labels are located on the inside of the housing cover Setup of the feedback on the actuator position using proximity switches 1 Loosen the screws for the housing cove...

Страница 35: ...t parameter values Incorrect parameter values can cause the valve to move unexpectedly This can lead to process failures and result in injuries Before recommissioning a positioner that was previously...

Страница 36: ...g to the function desired Operating button functions Control button Meaning ENTER Acknowledge message Start an action Save in the non volatile memory MODE Choose operating mode operating level Select...

Страница 37: ...its packaging are manufactured from materials that can be recycled by specialist recycling companies Bear the following points in mind when disposing of them As of 8 15 2018 this product will be under...

Страница 38: ...Company Address Contact person Telephone Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat...

Страница 39: ...TZIDC 200 DIGITAL POSITIONER CI TZIDC 200 C FM US EN REV B 39 Trademarks HART is a registered trademark of FieldComm Group Austin Texas USA...

Страница 40: ...prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document...

Отзывы: