background image

Periodic checks 

 

12 

TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN 

 

 

7 Periodic 

checks 

 

 

Safety inspections 

The safety function for the entire safety loop must be checked regularly in accordance with 
IEC 61508. The inspection intervals are defined when calculating the individual safety loops for 
a system. 
Users are responsible for selecting the type of check and the intervals within the specified 
period. The PFD

AV

 value depends on the selected inspection interval. For the PFD

AV

 values in 

the SIL declaration of conformity, the inspection interval T[Proof] for checking the safety function 
is 1 year. For other inspection intervals with corresponding PFD

AV

 values, refer to the section 

titled "Management summary FMEDA". 
Inspections must be conducted in a manner that enables users to verify the proper function of 
the safety equipment in combination with all components. 
One possible procedure for recurring tests to detect hazardous and unidentified device errors is 
described in the following section. This test is able to detect 99 % of the "Du" errors affecting the 
transmitter. 
 

Checking the safety function 

To check the safety function of the device, proceed as follows: 
1.  Bridge the safety DCS or take other appropriate measures to ensure the alarm is not 

triggered unintentionally. 

2.  Deactivate write protection (refer to the relevant operating instructions). 
3.  Use the EDD / DTM simulation command (Diagnostics / Simulation / Current Output) to set 

the transmitter's current output to a high alarm value. 

4.  Check whether the current output signal reaches this value. 
5.  Use the EDD / DTM simulation command to set the transmitter's current output to a low 

alarm value. 

6.  Check whether the current output signal reaches this value. 
7.  Activate write protection (refer to the relevant operating instructions) and wait at least 

20 seconds. 

8.  Shut down and restart the device. 
9.  Check the current output with reference temperature; use 2-point calibration for the LRV 

value (lower measuring range limit 4 mA) and the URV value (upper measuring range limit 
20 mA). 

10. Remove the bridge from the safety DCS or use another method to restore normal operating 

conditions. 

11. After performing the test, the events must be documented and archived accordingly. 
 
An appropriate simulator (Pt100 simulator, reference voltage sources) can also be used to 
check the transmitter without sensor. The sensor has to be tested in accordance with the SIL 
requirements of the customer application. SensyTemp TSP temperature sensors can be tested 
in accordance with the OI/TSP by means of a quick check. 
 

Содержание TTH300 Series

Страница 1: ...SIL Safety Instructions SM TTX200 TTX300 SIL EN Temperature Transmitter TTH200 TTR200 TTH300 TTF300 TTF350 Information about functional safety...

Страница 2: ...el 49 551 905 534 Fax 49 551 905 555 Customer service center Phone 49 180 5 222 580 Fax 49 621 381 931 29031 automation service de abb com Copyright 2010 by ABB Automation Products GmbH Subject to cha...

Страница 3: ...applicable documents and papers 7 5 Terms and definitions 8 6 Safety function 9 6 1 Measuring point for SIL 2 Single configuration 10 6 2 Measuring point for SIL 3 Dual configuration 11 7 Periodic ch...

Страница 4: ...hazardous failures for a safety function on demand PFDAVG Average Probability of Failure on Demand Average probability of hazardous failures for a safety function on demand D Dangerous Rate of hazardo...

Страница 5: ...hich the request rate for the safety related system is not more than once a year and not greater than twice the frequency of the retest DCS Distributed Control System Control system used in industrial...

Страница 6: ...medium load according to data sheet specification sensor exposed to temperature and mechanical load high stress High load according to data sheet specification sensor exposed to temperature and mecha...

Страница 7: ...ommissioning instructions TTR200 DS TTR200 Data sheet TTR200 OI TTR200 Operating instructions TTR200 CI TTR200 Commissioning instructions TTH300 DS TTH300 Data sheet TTH300 OI TTH300 Operating instruc...

Страница 8: ...A safety related system carries out the safety functions that are required to achieve or maintain a safe state e g for a system Example A pressure meter a logics unit e g limit transmitter and a valve...

Страница 9: ...s is the factory setting LOW ALARM low alarm minimum alarm current The low alarm current can be configured in a range from 3 5 4 0 mA The factory setting is 3 6 mA The high alarm current can be config...

Страница 10: ...H300 H TTF300 H and TTF350 H with connected sensor inclusive of the housing and the process connections used The information in the corresponding documentation must be taken into consideration Overall...

Страница 11: ...onfiguration Two transmitters DCS for SIL3 A00264 B G C J J A F E E D H Fig 2 A Sensor 1 B Transmitter 1 C DCS D Measuring circuit 1 E Interface for LCD indicator F Sensor 2 G Transmitter 2 H Measurin...

Страница 12: ...Bridge the safety DCS or take other appropriate measures to ensure the alarm is not triggered unintentionally 2 Deactivate write protection refer to the relevant operating instructions 3 Use the EDD D...

Страница 13: ...ce the safety function has been checked the device must be write protected to prevent changes to the setup since any change to the measurement system or parameters will impair the safety function To e...

Страница 14: ...Parameterize Current Output Damping and change the damping value for example Then select Save Device Data in Device and check whether the message Device is write protected is displayed Warning The so...

Страница 15: ...safety instructions For redundancy mode with drift monitoring the following parameters must be set in DTM EDD on the TTH300 H TTF300 H and TTF350 H Redundancy mode on the TTH300 H TTF300 H and TTF350...

Страница 16: ...ngineering parameters 16 TTH200 TTR200 TTH300 TTF300 TTF350 SM TTX200 TTX300 SIL EN 9 Safety engineering parameters The safety relevant technical parameters are specified in the SIL declaration of con...

Страница 17: ...Namur NE 93 SM TTX200 TTX300 SIL EN TTH200 TTR200 TTH300 TTF300 TTF350 17 10 Namur NE 93 TTH200 H TTR200 H TTH300 H TTF300 H and TTF350 H transmitters meet requirements according to Namur NE 93...

Страница 18: ...agement summary FMEDA Failure modes effects and diagnostic analysis 18 TTH200 TTR200 TTH300 TTF300 TTF350 SM TTX200 TTX300 SIL EN 11 Management summary FMEDA Failure modes effects and diagnostic analy...

Страница 19: ...Management summary FMEDA Failure modes effects and diagnostic analysis SM TTX200 TTX300 SIL EN TTH200 TTR200 TTH300 TTF300 TTF350 19...

Страница 20: ...Management summary FMEDA Failure modes effects and diagnostic analysis 20 TTH200 TTR200 TTH300 TTF300 TTF350 SM TTX200 TTX300 SIL EN...

Страница 21: ...Management summary FMEDA Failure modes effects and diagnostic analysis SM TTX200 TTX300 SIL EN TTH200 TTR200 TTH300 TTF300 TTF350 21...

Страница 22: ...Management summary FMEDA Failure modes effects and diagnostic analysis 22 TTH200 TTR200 TTH300 TTF300 TTF350 SM TTX200 TTX300 SIL EN...

Страница 23: ...Management summary FMEDA Failure modes effects and diagnostic analysis SM TTX200 TTX300 SIL EN TTH200 TTR200 TTH300 TTF300 TTF350 23...

Страница 24: ...herein without notice Printed in the Fed Rep of Germany 03 2010 ABB 2010 3KXT200005R4801 SM TTX200 TTX300 SIL EN ABB Limited Salterbeck Trading Estate Workington Cumbria CA14 5DS UK Tel 44 0 1946 830...

Отзывы: