Electrical
connections
CI/TTF300-X1
TTF300
EN - 21
4.4.1.3 Insulated sensor measuring inset (thermocouple, mV, RTD, ohms), transmitter housing not
grounded
The shields of the power supply cable and the sensor connecting cable are connected to one
another via the transmitter housing.
The shield is grounded at one end of the power supply cable, directly at the supply isolator /
PCS input.
Make sure that the shields are not connected to ground anywhere else.
A00272
4
1
2
3
6
5
8
7
Fig. 11: Shields of the sensor connecting cable and the power supply cable are connected electrically via the
transmitter housing and grounded at one end
1 Temperature
sensor
2
Shield insulated from sensor
3
Sensor connection cable
4
Shields connected electrically via transmitter
housing
5
Transmitter housing, not grounded
6
Power supply cable
7
Grounding point
8
Supply isolator / PCS input