Safety
6 - EN
TTF300
CI/TTF300-X1
1.4.2 Name
plate
1.4.3 Name plate: TTF300 - HART
The name plate is located on the transmitter housing.
A00265
Automation Products GmbH
Alzenau
Germany 2008
TTF300
TTF300
U = + 11...30 V, I = 4...20 mA, HART
Cfg: 1 x Pt100 3W; 0...100°C
TA. = -40°C...+85°C
S
a
O-Code: TTF300-E1H
2400045678
Ser.-No: 2065342
HW. Rev. 1.06
SW. Rev. 1.01.03
PTB 05 ATEX 2017 X
II 1 G Ex ia IIC T6
II 2(1) G Ex [ia]ib IIC T6
II 2G (1D) Ex [iaD]ib IIC T6
T1...T4 Ta. = -40 °C ... +60 °C (Zone 0) ... +85 °C (Zone 1)
T5
Ta. =
T6
Ta. =
TTF300-E1H;
-40 °C ... +56 °C (Zone 0) ... +71 °C (Zone 1)
-40 °C ... +44 °C (Zone 0) ... +56 °C (Zone 1)
IP20
13
14
15
16
10
8
4
7
5
3
2
12
11
6
9
1
Fig. 1: Example for ATEX explosion protection
1
Project number
2
Manufacturer of transmitter
3
Country and year of manufacture
4
Order number
5
Serial number
6
Supply voltage range, typical current
range, protocol
7
Customer configuration
8 Ambient temperature range / housing
degree of protection
9
Ex mark (optional)
10
Protection class of hazardous area
design (optional)
11
Temperature class of hazardous area
design (optional)
12
Refer to product documentation
13
Software revision number / hardware
revision number
14
CE mark (EC conformity)
15
Type designation
16
Safety integrity level (optional)