 ABB Transformer Protection Unit 2000R

4-9

Relay Design and Specifications

Built-In Testing

The TPU-2000R continuously checks itself for proper functioning.

Self-Test Status

The TPU-2000R provides continuous self-testing of its power supply voltages, memory elements, digital signal processor
and its program execution. In the event of a system failure, the protective functions are disabled and the Self-Check
Alarm contacts are actuated. Except for a “processor stalled” condition, review the PASS/FAIL status of these self-test
elements by using the man-machine interface (MMI). Normal status is indicated by a green TPU STATUS light (LED)
and system failure is indicated by a red TPU STATUS light (or by the green TPU STATUS light not being lit in the case
of a loss of control power).  If the green light is flashing, refer to the Operations Menu in Section 9.

Self-Test Failures are recorded as a number in the Operations Record. The binary bit pattern of this number indicates
the Self-Test Failure or Editor Access Status involved. The 1’s in the bit pattern indicate where a failure has occurred.
Count from the right of the bit pattern (starting with zero) to the position where a “1” occurs. Compare that bit position
with Table 4-1 to reveal the failure. See the following examples for further explanation.

If the self-test fails, the TPU-2000R is no longer providing protection. Replace the unit as soon as possible.

Table 4-1. Operations Record Value Information

Bit Position

Self-Test Failure

Editor Access Status

0

CPU RAM

INTERRUPT LOGGING

1

CPU EPROM

REMOTE EDIT DISABLE = 1

2

CPU NVRAM

LOCAL EDIT DISABLED = 1

3

CPU EEPROM

FRONT MMI EDIT ACTIVE

4

NOT USED

FRONT COMM PORT EDIT ACTIVE

5

NOT USED

REAR COMM PORT EDIT ACTIVE

6

NOT USED

REAR AUX COMM PORT EDIT ACTIVE

7

NOT USED

REAL TIME CLOCK EDITED

8

DSP ROM

PROGRAMMABLE I/O EDITED

9

DSP INTERNAL RAM

PRIMARY SET EDITED

10

DSP EXTERNAL RAM

ALTERNATE1 SETTINGS EDITED

11

DSP ANALOG/DIGITAL CONVETER

ALTERNATE2 SETTINGS EDITED

12

DSP +/-5 V POWER SUPPLY

CONFIGURATION SETTINGS EDITED

13

DSP +/-15 V POWER SUPPLY

COUNTER SETTINGS EDITED

14

DSP STALL or +5 V POWER SUPPLY

ALARM SETTINGS EDITED

15

DSP TO CPU COMMUNICATIONS

COMMUNICATIONS SETTINGS EDITED

#

#

Содержание TPU2000R

Страница 1: ...nd press E In the Change Settings menu scroll to Clock and set the unit clock At this point the internal battery is now in use If the unit is not going into service for an extended period set the day of the month to zero 0 and the battery will not be in use The battery will remain unused until the clock is set to a valid date Press E to enter the correct time and return to the Change Settings menu...

Страница 2: ...57 2 5 22 132 6 C E 594 15 1 STATUS NORMAL FAIL OVERTEMP OVERLOAD SYSTEM RESET A B C N DIFFERENTIAL TIME INSTANTANEOUS NEGATIVE SEQUENCE TARGET RESET TARGETS TPU 2000R RET 544 G 2 Top View 9 00 229 0 17 12 434 8 15 4 1 625 42 Bracket Position for Semi flush Mounting Bracket Position for Flush Mounting Figure 4 2 TPU 2000R Case Dimensions ...

Страница 3: ...he table Jumper 6 is used to set the TRIP Output Contact to Normally Open or Normally Closed Figure 4 3 Rear Terminal Block SENSOR 7 CONT INST BOOK SERIAL NO CATALOG NO TYPE GRD PHASE FREQ COM 1 COM 2 VN VC VB VA SENSOR 8 IN 1 VDC COM MON IN 2 IN 3 IN 4 IN 5 5 7 4 AUX PORTS 1 2 3 5 6 5 5 5 5 8 6 6 0 5 9 6 1 7 6 2 8 6 4 6 3 IN 6 IN 7 IN 8 3 1 3 2 3 3 3 4 3 9 4 0 4 1 SELF CHECK ALARM 1 1 9 1 0 1 2 1...

Страница 4: ... Press CR to continue The next screen to appear will be the Main Menu If com settings are not compatible or some other problem exists the Communication Status screen appears Reset the com settings and recheck connections and press CR The only option necessary for downloading the software update is the Update Unit Software selection Using the arrow keys scroll to the Update Unit Software selection ...

Страница 5: ...r Editor Access Status involved The 1 s in the bit pattern indicate where a failure has occurred Count from the right of the bit pattern starting with zero to the position where a 1 occurs Compare that bit position with Table 4 1 to reveal the failure See the following examples for further explanation If the self test fails the TPU 2000R is no longer providing protection Replace the unit as soon a...

Страница 6: ... table are stored in nonvolatile memory preventing data loss during control power cycling When you finish editing any settings table the changed table s data is transferred from a temporary edit buffer into three separate locations in nonvolatile memory A background diagnostics task continuously runs a checksum on each copy of the settings tables to verify data consistency If an invalid copy is de...

Страница 7: ...o reset LED targets and the LCD after a fault push C once scroll through all metered values push C twice reset the peak demand values push C three times Perform a system reset by simultaneously pressing the C E and up arrow keys This resets the microprocessor and re initiates the software program During a system reset no stored information or settings are lost The following displays and menus are ...

Страница 8: ...ings Alt2 Settings Configuration Counter Settings Alarm Settings Clock Communications RECORDS MENU Diff Fault Record Through Fault Record Operations Record Operations Summary SETTINGMENU Show Settings Change Settings Unit Information Password protected MAIN MENU Meter Settings Records Operations TEST MENU Self Test Contact Inputs Output Contacts UNIT INFORMATION CAT 588R0411 6111 SERIAL 951280 CPU...

Отзывы: